OPTIONS1 (Options 1 Configuration)
OPTIONS2 (Options 2 Configuration)
DESCRIPTION VALUE DEFAULT UNITS POINT NAME
Cooler Fluid 1 = Water
2 = Med. Brine
1FLUIDTYP
Minimum Load Vlv Select No/Yes No MLV_FLG
Return Gas Sensor Enable Dsable/Enable Dsable RGT_ENA
Motormaster Select No/Yes No MTR_TYPE
Cooler Pump Control Off/On Off CPC
Cooler Pump 1 Enable No/Yes No PMP1_ENA
Cooler Pump 2 Enable Dsable/Enable Dsable PMP2_ENA
Cooler Pmp Periodic Strt No/Yes No PUMP_PST
Cooler Pump Select 0 = Automatic
1 = Pump 1
2 = Pump 2
0 PMP_SLCT
Cooler Pump Shutdown Dly 0 to 10 1 minutes PUMP_DLY
Pump Changeover Hours 10 to 2000 500 hours PMP_DLTA
EMM Module Installed No/Yes No EMM_BRD
DESCRIPTION VALUE DEFAULT UNITS POINT NAME
Control Method 0 = Switch
2 = Occupancy
3 = SCN
0 CONTROL
Loading Sequence Select 1 = Equal Loading
2 = Staged Loading
1 SEQ_TYP
Lead/Lag Circuit Select 0 = Automatic
1 = Circuit A Leads
2 = Circuit B Leads
0LEAD_TYP
Cooling Setpoint Select 0 = Single
1 = Dual, remote switch controlled
2 = Dual SCN occupancy
3 = 4-20 mA input
0CLSP_TYP
Ramp Load Select Enable/Dsable Enable RAMP_EBL
Heat Cool Select Cool/Heat Cool HEATCOOL
High LCW Alert Limit 2 to 60 60.0
∆
∆∆
∆
F LCW_LMT
Minutes off time 0 to 15 0 min DELAY
Deadband Multiplier 1.0 to 4.0 2.0 Z_GAIN
Ice Mode Enable Enable/Dsable Dsable ICE_CNFG
Close Control Select Enable/Dsable Dsable CLS_CTRL
Low Sound Mode Select 0 = Disabled
1 = Fan only
2 = Capacity/Fans
1LS_MODE
Low Sound Start Time 00:00 to 23:59 00:00 LS_START
Low Sound End Time 00:00 to 23:59 00:00 LS_END
Low Sound Capacity Limit 0 to 100 100 % LS_LIMIT
Enable Short Loop Gain Enable/Dsable Enable SAGENABL