Sterling 30RA010-055 Refrigerator User Manual


 
82
UNIT
MAINTENANCE
ALARMS: Maintenance Display
DESCRIPTION VALUE DEFAULT UNITS POINT NAME
Compressor A1 Size 8 to 15
60 Hz: 010-10; 015-15;
018-9; 022-9; 025-13;
030-15; 035-9; 040-13;
045-10; 050-13; 055-15
50 Hz: 010-11; 015-7;
018-9; 022-11; 025-13;
032-8; 035-13; 042-11;
045-13
SIZE_A1
Compressor A2 Size 0 to 15
60 Hz: 018-9; 022-13;
025-13; 030-15; 035-13;
040-13;
045-13; 050-13; 055-15
50 Hz: 015-7; 018-9; 022-
11; 025-13; 032-11; 035-
13; 042-11; 045-13
SIZE_A2
Compressor B1 Size 0 to 15
60 Hz: 035-15; 040-15;
045-10; 050-13; 055-15
50 Hz: 032-13; 035-13;
042-11; 045-13
SIZE_B1
Compressor B2 Size 0 to 15
60 Hz: 045-13; 050-13;
055-15
50 Hz: 042-11; 045-13
SIZE_B2
Suction Superheat Setpt 10 to 40 15 SH_SP
Refrigerant 1 = R22 1 REFRIG_T
Fan Staging Select 1 = 1 Fan
2 = 2 Fans
3 = 3 Fans
4 = 4 Fans
1 = One Fan (010-018)
2 = Two Fans (022-030)
3 = Three Fans (032-040)
4 = Four Fans (042-055)
FAN_TYPE
DESCRIPTION VALUE POINT NAME
Active Alarm #1 Axxx or Txxx ALARM01C
Active Alarm #2 Axxx or Txxx ALARM02C
Active Alarm #3 Axxx or Txxx ALARM03C
Active Alarm #4 Axxx or Txxx ALARM04C
Active Alarm #5 Axxx or Txxx ALARM05C
Active Alarm #6 Axxx or Txxx ALARM06C
Active Alarm #7 Axxx or Txxx ALARM07C
Active Alarm #8 Axxx or Txxx ALARM08C
Active Alarm #9 Axxx or Txxx ALARM09C
Active Alarm #10 Axxx or Txxx ALARM10C
Active Alarm #11 Axxx or Txxx ALARM11C
Active Alarm #12 Axxx or Txxx ALARM12C
Active Alarm #13 Axxx or Txxx ALARM13C
Active Alarm #14 Axxx or Txxx ALARM14C
Active Alarm #15 Axxx or Txxx ALARM15C
Active Alarm #16 Axxx or Txxx ALARM16C
Active Alarm #17 Axxx or Txxx ALARM17C
Active Alarm #18 Axxx or Txxx ALARM18C
Active Alarm #19 Axxx or Txxx ALARM19C
Active Alarm #20 Axxx or Txxx ALARM20C
Active Alarm #21 Axxx or Txxx ALARM21C
Active Alarm #22 Axxx or Txxx ALARM22C
Active Alarm #23 Axxx or Txxx ALARM23C
Active Alarm #24 Axxx or Txxx ALARM24C
Active Alarm #25 Axxx or Txxx ALARM25C