CURRMODS: Maintenance Display
DUALCHIL: Maintenance Display
DESCRIPTION VALUE POINT NAME
FSM controlling Chiller On/Off MODE_1
WSM controlling Chiller On/Off MODE_2
Master/Slave control On/Off MODE_3
Ramp Load Limited On/Off MODE_5
Timed Override in effect On/Off MODE_6
Low Cooler Suction TempA On/Off MODE_7
Low Cooler Suction TempB On/Off MODE_8
Slow Change Override On/Off MODE_9
Minimum OFF time active On/Off MODE_10
Dual Setpoint On/Off MODE_13
Temperature Reset On/Off MODE_14
Demand/Sound Limited On/Off MODE_15
Cooler Freeze Protection On/Off MODE_16
Low Temperature Cooling On/Off MODE_17
High Temperature Cooling On/Off MODE_18
Making ICE On/Off MODE_19
Storing ICE On/Off MODE_20
High SCT Circuit A On/Off MODE_21
High SCT Circuit B On/Off MODE_22
Minimum Comp. On Time On/Off MODE_23
Pump Off Delay Time On/Off MODE_24
Low Sound Mode On/Off MODE_25
Short Loop Override On/Off MODE_26
DESCRIPTION VALUE UNITS POINT NAME
Dual Chiller Link Good? Yes/No DC_LINK
Master Chiller Role Stand Alone,
Lead Chiller,
Lag Chiller
MC_ROLE
Slave Chiller Role Stand Alone,
Lead Chiller,
Lag Chiller
SC_ROLE
Lead Chiller Ctrl Point snnn.n
°
°°
°
FLEAD_CP
Lag Chiller Ctrl Point snnn.n
°
°°
°
FLAG_CP
Control Point snnn.n
°
°°
°
F CTRL_PNT
Cool EnteringFluid-Slave snnn.n
°
°°
°
FCOOLEWTS
Cool Leaving Fluid-Slave snnn.n
°
°°
°
F COOLLWTS
Cooler Entering Fluid snnn.n
°
°°
°
F COOL_EWT
Cooler Leaving Fluid snnn.n
°
°°
°
FCOOL_LWT
Lead/Lag Leaving Fluid snnn.n
°
°°
°
F DUAL_LWT
Percent Avail.Capacity 0-100 % CAP_A
Percent Avail.Cap.Slave 0-100 % CAP_A_S
Lag Start Delay Time hh:mm LAGDELAY
Load/Unload Factor snnn.n SMZ
Load/Unload Factor-Slave snnn.n SMZSLAVE
Lead SMZ Clear Commanded Yes/No LEADSMZC
Lag- SMZ Clear Commanded Yes/No LAG_SMZC
Lag Commanded Off? Yes/No LAG_OFF
Dual Chill Lead CapLimit 0-100 % DCLDCAPL
Dual Chill Lag CapLimit 0-100 % DCLGCAPL