ALARMDEF (Alarm Definition Table)
BRODEFS (Broadcast POC Definition Table)
DISPLAY (Marquee Display SETUP)
DUALCHIL (Dual Chiller Configuration Settings)
DESCRIPTION VALUE DEFAULT UNITS POINT NAME
Alarm Routing Control 00000000 00000000 ALRM_CNT
Equipment Priority 0 to 7 4 EQP_TYPE
Comm Failure Retry Time 1 to 240 10 min RETRY_TM
Re-alarm Time 1 to 255 30 min RE-ALARM
Alarm System Name XXXXXXXX CHILLER ALRM_NAM
DESCRIPTION VALUE DEFAULT UNITS POINT NAME
SCN Time/Date Broadcast Yes/No No SCNBC
SCN OAT Broadcast Yes/No No OATBC
Global Schedule Broadcast Yes/No No GSBC
SCN Broadcast Acker Yes/No No SCNBCACK
Daylight Savings Start:
Month 1 to 12 4 STARTM
Week 1 to 5 1 STARTW
Day 1 to 7 7 STARTD
Minutes to Add 0 to 99 60 min MINADD
Daylight Savings Stop
Month 1 to 12 10 STOPM
Week 1 to 5 5 STOPW
Day 1 to 7 7 STOPD
Minutes to Subtract 0 to 99 60 min MINSUB
DESCRIPTION VALUE DEFAULT UNITS POINT NAME
Service Password nnnn 1111 PASSWORD
Password Enable Enable/Disable Enable PASS_EBL
Metric Display Off/On Off DISPUNIT
Language Selection 0 = ENGLISH
1 = FRANCAIS
2 = ESPANOL
3 = PORTUGUES
0LANGUAGE
DESCRIPTION VALUE DEFAULT UNITS POINT NAME
LEAD/LAG
Lead/Lag Chiller Enable Enable/Dsable Dsable LL_ENA
Master/Slave Select Master/Slave Master MS_SEL
Slave Address 0 to 239 2 SLV_ADDR
Lead/Lag Balance Select 0 = None 0 LL_BAL
Lead/Lag Balance Delta 40 to 400 168 hours LL_BAL_D
Lag Start Delay 0 to 30 5 minutes LL_DELAY
Parallel Configuration Yes Yes PARALLEL