Henny Penny 500 Fryer User Manual


 
Model 500/600
The electric fryer requires 208 or 240 volt, three phase, 50/60
Hertz service. The power cord may be already attached to the
fryer or provided at installation. Check the data plate behind the
front door to determine the correct power supply.
This fryer
must be adequately and safely grounded (earthed)
or electrical shock could result. Refer to local electrical
codes for correct grounding (earthing) procedures or in
absence of local codes, with The National Electrical Code,
ANSI/NFPA No. 70-(the current edition). In Canada, all
electrical connections are to be made in accordance with CSA
C22.1, Canadian Electrical Code Part 1, and/or local codes.
To avoid electrical shock, this appliance must be equipped
with an external circuit breaker which will disconnect all
ungrounded (unearthed) conductors. The main power switch
on this appliance does
not disconnect all line conductors.
A separate disconnect switch with proper capacity fuses or breakers
must be installed at a convenient location between the fryer and the
power source. It should be an insulated copper conductor rated for
600 volts and 90
o
C. For runs longer than 50 feet (15.24 m), use the
next larger wire size.
Supply Wiring and Fusing for Electric Fryer
Supply Min.
Wire Fuse
Volts Phase KW Amps Size Size
208 Single 13.50 65 2 90
208 Three 13.50 38 6 50
240 Single 13.50 61 3 70
240 Three 13.50 35 6 50