Henny Penny 500 Fryer User Manual


 
Model 500/600
5-4. INFORMATION MODE
DETAILS
14. ANALOG <1> 2344
This step displays the present status of any channel of the controller’s a
to d converter. This feature may be useful to a technician
troubleshooting a problem with the fryer or controller.
The displayed value can be toggled between volts and bits by pressing
. If the displayed value has a decimal point, it is voltage
(0 to 5 VDC). If no decimal point is shown, the value is a-to-d bits
(0 - 4095).
Press to continue onto AC volts reading.
15. AC VOLTS 98%
This item displays the present status of the line voltage supply to the
fryer. The displayed value is averaged over a 10-second period, so
brief dips or fluctuations in the voltage might not show up in this display.
The voltage is normally displayed as a “percent of nominal” value,
where 100% would indicate that voltage is right on the nominal value
(i.e. 208 volts for a 208v fryer). The display can be toggled to an
actual Voltage value by pressing .
Press to continue onto AMPS reading.
16. AMPS 33 33 33
For electric fryers, this display shows the present readings from the
fryer’s amps sensors, which monitor the electrical current supplied to
the heaters. (These sensors are not present on gas fryers.)
On pressure fryers, these values indicate the current through each
supply leg to the heaters. These values do not correspond directly to
the current through an individual heater coil.
The amps values should normally cycle on and off with the heat light,
and all three values should be about the same.
Press and hold to exit Information Mode at any time, or after 2
minutes, controls automatically exit back to normal operation.