Mitsubishi Electronics SW2D5C-GTD2-E Frozen Dessert Maker User Manual


 
8 - 21
8.6 Error Code and Error Message List
8.6.1 GOT error code list
*1 When an error occurs, "FFH" is stored to the channel No.
804
The cable on the IN side
is disconnected or is not
connected.
Refer to explanations of SB0067 in the applicable network
manual.
805
The cable on the OUT
side is disconnected or is
not connected.
Refer to explanations of SB0068 in the applicable network
manual.
850
CC-Link switch setting
error
• Check if the switch settings have no error.
• Check error codes stored in SW006A.
• Refer to explanations of SB006A in the applicable network
manual.
851
Abnormal cyclic
transmission status
• Check if terminating resistors are connected.
• Check error codes for the PLC CPU.
• Check the parameter for the PLC CPU on the master
station.
• Check the error status of the master station.
• Refer to explanations of SB006E in the applicable network
manual.
852 Abnormal host line status
• Check if the cable is unplugged or not.
• Refer to explanations of SB0090 in the applicable network
manual.
853 Transient error
• Check the transient error occurrence status for each station
stored in SW0094 to SW0097.
• Refer to explanations of SB0049 in the applicable network
manual
Error
code
Error message Action
Channel
No.
storage