93
Parameter list
Parameter list
5
ADJUSTMENT
Monitor display and monitor output signal — Changing DU/PU monitored items and
clearing cumulative monitors (Pr.52, Pr.170, Pr.171, Pr.268, Pr.563, Pr.564, Pr.891)
52
DU/PU main display
data selection
10
0, 5, 6, 8 to 14,
17, 20, 23 to
25, 50 to 57,
100
Select the monitor to be displayed on the
operation panel and parameter unit.
The setting value of "9" is available only for the
75K or higher.
170
Watt-hour meter clear
1 9999
0
Set "0" to clear the watt-hour meter monitor.
×
10
Set the maximum value when monitoring from
communication to 0 to 9999kWh.
9999
Set the maximum value when monitoring from
communication to 0 to 65535kWh.
171
Operation hour meter
clear
1 9999 0, 9999
Set "0" to clear the operation time monitor.
Setting "9999" has no effect.
×××
268
Monitor decimal digits
selection
1 9999
0 Displays the monitor as integral value.
1 Displays the monitor in increments of 0.1.
9999 No fixed decimal position
563
Energization time
carrying-over times
1 0 (0 to 65535)
The numbers of cumulative energization time
monitor exceeded 65535h is displayed.
Reading only
×××
564
Operating time
carrying-over times
1 0 (0 to 65535)
The numbers of operation time monitor
exceeded 65535h is displayed.
Reading only
×××
891
Cumulative power
monitor digit shifted
times
1 9999
0 to 4
Set the number of times to shift the cumulative
power monitor digit.
Clamps the monitor value at maximum.
9999
No shift
Clears the monitor value when it exceeds the
maximum value.
Monitor display and monitor output signal — Changing the monitored item to be output
from terminal FM/AM
(Pr.54 to Pr.56, Pr.158, Pr.867)
54
FM terminal function
selection
11
1 to 3, 5, 6,
8 to 14, 17, 21,
24, 50, 52, 53
Select the monitor output to terminal FM.
The setting value of "9" is available only for the
75K or higher.
55
Frequency monitoring
reference
0.01Hz 60Hz
*2
0 to 400Hz
Set the full-scale value to output the output
frequency monitor value to terminal FM and
AM.
56
Current monitoring
reference
0.01/
0.1A
*1
Rated
inverter
current
*2
0 to 500/
0 to 3600A
*1
Set the full-scale value to output the output current
monitor value to terminal FM and AM.
158
AM terminal function
selection
11
1 to 3, 5, 6,
8 to 14, 17, 21,
24, 50, 52, 53
Select the monitor output to terminal AM.
The setting value of "9" is available only for the
75K or higher.
867
AM output filter
0.01s 0.01s 0 to 5s Set the output filter of terminal AM.
*1 The setting depends on the inverter capacity (55K or lower/75K or higher)
*2 Performing IPM parameter initialization changes the settings. (Refer to page 43)