Mitsubishi Electronics FR-F700P Microwave Oven User Manual


 
99
Parameter list
Parameter list
5
ADJUSTMENT
Communication operation and setting Initial setting of RS-485 communication
(Pr.117 to Pr.124, Pr.551)
Communication operation and setting Control of parameter write by communication
(Pr.342)
117
PU communication
station number
1 0 0 to 31
Specify the inverter station number.
Set the inverter station numbers when two or
more inverters are connected to one personal
computer.

118
PU communication
speed
1192
48, 96, 192,
384
Set the communication speed.
The setting value ×
100 equals the
communication speed.
For example, the communication speed is
19200bps when the setting value is "192".

119
PU communication
stop bit length
11
Stop bit length data length

0 1bit 8bit
1 2bit 8bit
10 1bit 7bit
11 2bit 7bit
120
PU communication
parity check
12
0 Without parity check

1 With odd parity check
2 With even parity check
121
Number of PU
communication retries
11
0 to 10
Set the permissible number of retries at
occurrence of a data receive error.
If the number of consecutive errors exceeds
the permissible value, the inverter trips.

9999
If a communication error occurs, the inverter
will not come to trip.
122
PU communication
check time interval
0.1s 9999
0 No PU connector communication

0.1 to 999.8s
Set the communication check time interval.
If a no-communication state persists for longer
than the permissible time, the inverter trips.
9999 No communication check
123
PU communication
waiting time setting
1 9999
0 to 150ms
Set the waiting time between data transmission
to the inverter and response.

9999 Set with communication data.
124
PU communication
CR/LF selection
11
0 Without CR/LF

1With CR
2With CR/LF
342
Communication
EEPROM write
selection
10
0
Parameter values written by communication are
written to the EEPROM and RAM.

1
Parameter values written by communication
are written to the RAM.
551
PU mode operation
command source
selection
12
1
Select the RS-485 terminals as the PU
operation mode control source.

2
Select the PU connector as the PU operation
mode control source.
Parameter
Name
Incre-
ments
Initial
Value
Range Description
Parameter
copy
Parameter
clear
All parameter
clear
Related
parameters
: enabled
× : disabled