Mitsubishi Electronics FR-F700P Microwave Oven User Manual


 
119
6
TROUBLESHOOTING
Causes and corrective actions
Operation Panel
Indication
Er4
Name
Mode designation error
Description
· You attempted to make parameter setting in the NET operation mode when Pr. 77 is not "2".
· If a parameter write was performed when the command source is not at the operation panel (FR-
DU07).
Check point
· Check that operation mode is "PU operation mode".
· Check the Pr. 77 setting. ( Refer to Chapter 4 of the Instruction Manual (Applied).)
· Check the Pr. 551 setting.
Corrective action
·
After setting the operation mode to the "PU operation mode", make parameter setting.
(Refer to page 78.)
· After setting "2" in Pr. 77, make parameter setting.
·Set Pr.551 = "2 (initial setting)". ( Refer to Chapter 4 of the Instruction Manual (Applied).)
Operation Panel
Indication
rE1
Name
Parameter read error
Description
An error occurred in the EEPROM on the operation panel side during parameter copy reading.
Check point
--------------
Corrective action
· Make parameter copy again. (Refer to page 80.)
· Check for an operation panel (FR-DU07) failure. Please contact your sales representative.
Operation Panel
Indication
rE2
Name
Parameter write error
Description
· You attempted to perform parameter copy write during operation.
· An error occurred in the EEPROM on the operation panel side during parameter copy writing.
Check point
Is the FWD or REV LED of the operation panel (FR-DU07) lit or flickering?
Corrective action
· After stopping the operation, make parameter copy again. (Refer to page 80.)
· Check for an operation panel (FR-DU07) failure. Please contact your sales representative.
Operation Panel
Indication
rE3
Name
Parameter verification error
Description
· Data on the operation panel side and inverter side are different.
· An error occurred in the EEPROM on the operation panel side during parameter verification.
Check point
Check for the parameter setting of the source inverter and inverter to be verified.
Corrective action
· Press to continue verification.
Make parameter verification again. (Refer to page 81.)
· Check for an operation panel (FR-DU07) failure. Please contact your sales representative.
Operation Panel
Indication
rE4
Name
Model error
Description
· A different model was used for parameter writing and verification during parameter copy.
· When parameter copy write is stopped after parameter copy read is stopped.
Check point
· Check that the verified inverter is the same model.
· Check that the power is not turned OFF or an operation panel is not disconnected, etc. during
parameter copy read.
Corrective action
· Use the same model (FR-F700(P) series) for parameter copy and verification.
· Perform parameter copy read again.
Operation Panel
Indication
Err.
Description
· The RES signal is ON.
· The PU and inverter cannot make normal communication (contact fault of the connector).
· When the voltage drops in the inverter's input side.
· While the control circuit power (R1/L11, S1/L21) and the main circuit power (R/L1, S/L2, T/L3) are
connected to separate power sources, the error may appear when turning ON the main circuit. This
is not a fault though.
Corrective action
· Turn OFF the RES signal.
· Check the connection of PU and the inverter.
· Check the voltage on the inverter's input side.