71
Simple mode parameter list
Simple mode parameter list
5
ADJUSTMENT
5 ADJUSTMENT
5.1 Simple mode parameter list
For simple variable-speed operation of the inverter, the initial setting of the parameters may be used as they are. Set
the necessary parameters to meet the load and operational specifications. Parameter setting, change and check can
be made from the operation panel (FR-DU07). For details of parameters, refer to Chapter 4 of the Instruction
Manual (Applied).
POINT
Only simple mode parameters are displayed by the initial setting of Pr. 160 User group read selection. Set Pr. 160 User
group read selection as required. (Refer to page 51 for parameter change.)
Pr. 160 Description
9999
(Initial Value)
Only the simple mode parameters can be displayed.
0 Simple mode and extended mode parameters can be displayed.
1 Only the parameters registered in the user group can be displayed.
Parameter
Number
Name
Incre
ments
Initial
Value
Range Applications
Refer
to
0
Torque boost
0.1%
6/4/3/2/
1.5/1%
*1
0 to 30%
Set to increase a starting torque or when the
motor with a load will not rotate, resulting in an
alarm [OL] and a trip [OC1]
73
1
Maximum
frequency
0.01Hz
120/
60Hz
*2,
*3
0 to 120Hz
Set when the maximum output frequency need
to be limited.
74
2
Minimum
frequency
0.01Hz 0Hz 0 to 120Hz
Set when the minimum output frequency need
to be limited.
3
Base frequency
0.01Hz 60Hz 0 to 400Hz
Set when the rated motor frequency is 50Hz.
Check the motor rating plate.
53
4
Multi-speed setting
(high speed)
0.01Hz 60Hz *3 0 to 400Hz
Set when changing the preset speed in the
parameter with a terminal.
655
Multi-speed setting
(middle speed)
0.01Hz 30Hz 0 to 400Hz
6
Multi-speed setting
(low speed)
0.01Hz 10Hz 0 to 400Hz
7 Acceleration time
0.1s 5/15s *4 0 to 3600s
Acceleration/deceleration time can be set. 75
8 Deceleration time
0.1s 10/30s *4 0 to 3600s
9
Electronic thermal
O/L relay
0.01/
0.1A
*5
Rated
inverter
current
*3
0 to 500/
0 to 3600A
*5
Protect the motor from overheat by the inverter.
Set the rated motor current.
52
60
Energy saving
control selection
100, 4, 9
The inverter output voltage is minimized when
using for fan and pump applications.
76
79
Operation mode
selection
1 0 0, 1, 2, 3, 4, 6, 7
Select the start command location and
frequency setting location.
78
125
Terminal 2
frequency setting
gain frequency
0.01Hz 60Hz *3 0 to 400Hz
Frequency for the maximum value of the
potentiometer (at 5V) can be changed.
68
126
Terminal 4
frequency setting
gain frequency
0.01Hz 60Hz *3 0 to 400Hz
Frequency at 20mA input can be changed. 70
160
User group read
selection
1 9999 0, 1, 9999
Make extended parameters valid
—
V/F
V/F
V/F
V/F
V/F
V/F
S
MFVC
S
MFVC
S
MFVC
V/F
V/F
V/F