Parameter list
Parameter list
5
ADJUSTMENT
Frequency setting with terminals (contact input) Remote setting function (Pr.59)
59
Remote function
selection
10
0
RH, RM, RL signal
function
Frequency setting
storage function

Multi-speed setting
1
Remote setting
Used
2 Not used
3
No (Turning STF/STR
OFF clears remotely-
set frequency.)
11
Remote setting
(These setting values
enable deceleration to
the frequency lower
than the set
frequency.)
Used
12 Not used
13
Not used (Turning
STF/STR OFF clears
remotely-set
frequency.)
Energy saving operation Energy saving control selection (Pr.60)
60
Energy saving control
selection
10
0 Normal operation mode

4 Energy saving operation mode
9 Optimum excitation control mode
Operation setting at fault occurrence Retry at fault occurrence (Pr.65, Pr.67 to Pr.69)
65
Retry selection
1 0 0 to 5 A fault for retry can be selected.

67
Number of retries at
fault occurrence
10
0 No retry function

1 to 10
Set the number of retries at fault occurrence. A
fault output is not provided during retry
operation.
101 to 110
Set the number of retries at fault occurrence.
(The setting value - 100 is the number of
retries.) A fault output is provided during retry
operation.
68
Retry waiting time
0.1s 1s 0 to 10s
Set the waiting time from when an inverter fault
occurs until a retry is made.

69
Retry count display
erase
100
Clear the number of restarts succeeded by
retry.

66
Refer to Pr.22 and Pr.23.
67 to 69
Refer to Pr.65.
70
Refer to Pr.30.
Selection and protection of a motor Motor selection (general-purpose motor, IPM
motor) (Pr.71)
71
Applied motor
10 *
0
Thermal characteristics of a standard motor

1
Thermal characteristics of the Mitsubishi
constant-torque motor
2
Thermal characteristic of standard motor
Adjustable 5 points V/F
20
Mitsubishi standard motor (SF-JR 4P 1.5kW or
less)
120
High-efficiency IPM motor MM-EF
210
Premium high-efficiency IPM motor MM-EFS
* Performing IPM parameter initialization changes the settings. (Refer to page 43)
Parameter
Name
Incre-
ments
Initial
Value
Range Description
Parameter
copy
Parameter
clear
All parameter
clear
Related
parameters
: enabled
× : disabled
V/F
V/F