Mitsubishi Electronics FR-F700P Microwave Oven User Manual


 
171
The EU Directives are issued to standardize different national regulations of the EU Member States and to facilitate free movement of the
equipment, whose safety is ensured, in the EU territory.
Since 1996, compliance with the EMC Directive that is one of the EU Directives has been legally required. Since 1997, compliance with the
Low Voltage Directive, another EU Directive, has been also legally required. When a manufacturer confirms its equipment to be compliant
with the EMC Directive and the Low Voltage Directive, the manufacturer must declare the conformity and affix the CE marking.
The authorized representative in the EU
The authorized representative in the EU is shown below.
Name: Mitsubishi Electric Europe B.V.
Address: Gothaer Strasse 8, 40880 Ratingen, Germany
Note
We declare that this inverter conforms with the EMC Directive in industrial environments and affix the CE marking on the inverter. When
using the inverter in a residential area, take appropriate measures and ensure the conformity of the inverter used in the residential area.
(1) EMC Directive
We declare that this inverter conforms with the EMC Directive and affix the CE marking on the inverter.
EMC Directive: 2004/108/EC
Standard(s): EN61800-3:2004 (Second environment / PDS Category "C3")
Note: First environment
Environment including residential buildings. Includes buildings directly connected without a transformer to the low voltage power
supply network which supplies power to residential buildings.
Second environment
Environment including all buildings except buildings directly connected without a transformer to the low voltage power supply
network which supplies power to residential buildings.
Note
Set the EMC filter valid and install the inverter and perform wiring according to the following instructions.
* The inverter is equipped with a built-in EMC filter. Set the EMC filter valid. (The EMC filter is invalid when shipped from the factory. (The
FR-F720P-0.75K and 1.5K are always valid.) For details, refer to page 10.)
* Connect the inverter to an earthed power supply.
* Install a motor and a control cable according to the instructions written in the EMC Installation Guidelines (BCN-A21041-204 (For the
manual, please contact your sales representative.) ).
* The cable length between the inverter and the motor is 5 m maximum.
* Confirm that the final integrated system with the inverter conforms with the EMC Directive.
* This inverter does not conform with the EU Directives when used with an IPM motor.
Appendix 4 Instructions for compliance with the EU Directives