60
Start/stop from the operation panel (PU
operation mode)
4.4.5 Setting the frequency by analog input (current input)
[Connection diagram]
POINT
· Use or on the operation panel (FR-DU07) to give a start command.
· Use the current signal source (4 to 20mA) (by connecting terminal 4 and 5) to give a frequency command.
· Switch ON the AU signal.
· Set "4" (External/PU combination operation mode 2) in Pr. 79 Operation mode selection.
Operation example Performing operation at 60Hz.
Operation Display
1. Screen at power-ON
The monitor display appears.
2. Operation mode setting
Set "4" in Pr.79.
[PU] indicator and [EXT] indicator are lit.
(To change the set value, refer to page 48)
3. Start
Check that the terminal 4 input selection signal (AU) is ON.
Press or
[FWD] or [REV] is flickering as no frequency command is given.
/
4. Acceleration → constant speed
Perform 20mA input.
The frequency on the display increases in the Pr. 7 Acceleration
time, and " " (60.00Hz) appears.
5. Deceleration
Input 4mA or less.
The frequency on the display decreases in the Pr. 8 Deceleration
time, and the motor stops rotating with " " (0.00Hz)
displayed. [FWD] indicator or [EXT] indicator flickers.
6. Stop
Press
[FWD] indicator or [REV] indicator turns OFF.
REMARKS
Pr. 184 AU terminal function selection must be set to "4" (AU signal) (initial value). (Refer to Chapter 4 of the Instruction
Manual (Applied).)
Change the frequency (60Hz) at the maximum current input (at 20mA, initial value)
Adjust the frequency in Pr. 126 Terminal 4 frequency setting gain frequency. (Refer to page 70.)
Change the frequency (0Hz) at the minimum current input (at 4mA, initial value)
Adjust the frequency in calibration parameter C5 Terminal 4 frequency setting bias frequency. (Refer to
Chapter 4 of the Instruction Manual (Applied).)
Inverter
Operation panel
(FR-DU07)
Current signal
source
(4 to 20mADC)
5 (-)
4 (+)
SD
AU
AU signal
Flickering
Current signal
source
(20mADC)
Current signal
source
(4mADC)
Flickering
Stop