Mitsubishi Electronics FR-F700P Microwave Oven User Manual


 
27
Wiring
2
INSTALLATION AND WIRING
2.4.9 RS-485 terminal block
2.4.10 Communication operation
Using the PU connector or RS-485 terminal, you can
perform communication operation from a personal
computer etc. When the PU connector is connected
with a personal, FA or other computer by a
communication cable, a user program can run and
monitor the inverter or read and write to parameters.
For the Mitsubishi inverter protocol (computer link
operation), communication can be performed with the
PU connector and RS-485 terminal.
For the Modbus-RTU protocol, communication can be
performed with the RS-485 terminal.
For further details,
refer to Chapter 4 of the
Instruction Manual (Applied).
Conforming standard: EIA-485(RS-485)
Transmission format: Multidrop link
Communication speed: MAX 38400bps
Overall length: 500m
Connection cable:Twisted pair cable
(4 pairs)
RXD
RDA1
(RXD1+)
RDB1
(RXD1-)
RDA2
(RXD2+)
RDB2
(RXD2-)
SDA1
(TXD1+)
SDB1
(TXD1-)
SDA2
(TXD2+)
SDB2
(TXD2-)
P5S
(VCC)
SG
(GND)
P5S
(VCC)
SG
(GND)
VCC
TXD
OPEN
100Ω
Terminating resistor switch
Factory-set to "OPEN".
Set only the terminating resistor switch of
the remotest inverter to the "100Ω" position.
Programmable controller
Multidrop link
(32 inverters
maximum are
connectable)
Inverter Inverter Inverter