CL-6
19XR, XRV PIC II OPTIONS TABLE CONFIGURATION SHEET
DESCRIPTION RANGE UNITS DEFAULT VALUE
Auto Restart Option 0/1 DSABLE/ENABLE DSABLE
Remote Contacts Option 0/1 DSABLE/ENABLE DSABLE
Soft Stop Amps Threshold 40 to 100 % 100
Surge/Hot Gas Bypass
Surge Limit/HGBP Option
Select: Surge=0, HGBP=1
0/1 0
Min. Load Point (T1, P1)
Surge/HGBP Delta T1 0.5 to 20 ˆF1.5
Surge/HGBP Delta P1 30 to 170 PSI 50
Full Load Point (T2, P2)
Surge/HGBP Delta T2 0.5 to 20 ˆF10
Surge/HGBP Delta P2 50 to 170 PSI 85
Surge/HGBP Deadband 0.5 to 3 ˆF1
Surge Protection
Surge Delta% Amps 5 to 20 % 10
Surge Time Period 7 to 10 MIN 8
Ice Build Control
Ice Build Option 0/1 DSABLE/ENABLE DSABLE
Ice Build Termination
0=Temp, 1=Contacts, 2=Both
0 to 2 0
Ice Build Recycle 0/1 DSABLE/ENABLE DSABLE
Refrigerant Leak Option 0/1 DSABLE/ENABLE DSABLE
Refrigerant Leak Alarm mA 4 to 20 mA 20
Head Pressure Reference
Delta P at 0% (4 mA) 20 to 60 psi 25
Delta P at 100% (20 mA) 20 to 60 psi 35
Minimum Output 0 to 100 % 0