Carrier XRV Refrigerator User Manual


 
34
The PROPORTIONAL ECW GAIN can be adjusted on the
CVC/ICVC display for values of 1, 2, or 3; the default setting
is 2. Increase this setting to increase guide vane response to a
change in entering chilled water temperature.
DEMAND LIMITING The PIC II responds to the ACTIVE
DEMAND LIMIT set point by limiting the opening of the
guide vanes. It compares the ACTIVE DEMAND LIMIT set
point to the DEMAND LIMIT SOURCE (either the AVERAGE
LINE CURRENT or the MOTOR KW). Depending on how the
control is configured. DEMAND LIMIT SOURCE is on the
RAMP_DEM screen. The default source is the compressor
motor current.
CHILLER TIMERS The PIC II maintains 2 run time
clocks, known as COMPRESSOR ONTIME and SERVICE
ONTIME. COMPRESSOR ONTIME indicates the total life-
time compressor run hours. This timer can register up to
500,000 hours before the clock turns back to zero. The SER-
VICE ONTIME is a reset table timer that can be used to indi-
cate the hours since the last service visit or any other event.
The time can be changed from the CVC/ICVC to whatever
value is desired. This timer can register up to 32,767 hours
before it rolls over to zero.
The chiller also maintains a start-to-start timer and a stop-
to-start timer. These timers limit how soon the chiller can be
started. START INHIBIT TIMER is displayed on the MAIN-
STAT screen. See the Start-Up/Shutdown/Recycle Sequence
section, page 46, for more information on this topic.
OCCUPANCY SCHEDULE The chiller schedule, de-
scribed in the Time Schedule Operation section (page 20), de-
termines when the chiller can run. Each schedule consists of
from 1 to 8 occupied or unoccupied time periods, set by the op-
erator. The chiller can be started and run during an occupied
time period (when OCCUPIED? is set to YES on the MAIN-
STAT display screen). It cannot be started or run during an un-
occupied time period (when OCCUPIED? is set to NO on the
MAINSTAT display screen). These time periods can be set for
each day of the week and for holidays. The day begins with
0000 hours and ends with 2400 hours. The default setting for
OCCUPIED? is YES, unless an unoccupied time period is in
effect.
These schedules can be set up to follow a buildings occu-
pancy schedule, or the chiller can be set so to run 100% of the
time, if the operator wishes. The schedules also can be by-
passed by forcing the CHILLER START/STOP parameter on
the MAINSTAT screen to START. For more information on
forced starts, see Local Start-Up, page 46.
The schedules also can be overridden to keep the chiller in
an occupied state for up to 4 hours, on a one time basis. See the
Time Schedule Operation section, page 20.
Figure 19 shows a schedule for a typical office building
with a 3-hour, off-peak, cool-down period from midnight to
3 a.m., following a weekend shutdown. Holiday periods are in
an unoccupied state 24 hours per day. The building operates
Monday through Friday, 7:00 a.m. to 6:00 p.m., and Saturdays
from 6:00 a.m. to 1:00 p.m. This schedule also includes the
Monday midnight to 3:00 a.m. weekend cool-down schedule.
NOTE: This schedule is for illustration only and is not
intended to be a recommended schedule for chiller operation.
Whenever the chiller is in the LOCAL mode, it uses Occu-
pancy Schedule 01 (OCCPC01S). When the chiller is in the
ICE BUILD mode, it uses Occupancy Schedule 02
(OCCPC02S). When the chiller is in CCN mode, it uses
Occupancy Schedule 03 (OCCPC03S).
The CCN SCHEDULE NUMBER is configured on the
NET_OPT display screen, accessed from the EQUIPMENT
CONFIGURATION table. See Table 2, Example 15. SCHED-
ULE NUMBER can be changed to any value from 03 to 99. If
this number is changed on the NET_OPT screen, the operator
must go to the ATTACH TO NETWORK DEVICE screen to
upload the new number into the SCHEDULE screen. See
Fig. 18.
Safety Controls
The PIC II monitors all safety control
inputs and, if required, shuts down the chiller or limits the
guide vanes to protect the chiller from possible damage from
any of the following conditions:
high bearing temperature
high motor winding temperature
high discharge temperature
low discharge superheat*
low oil pressure
low cooler refrigerant temperature/pressure
condenser high pressure or low pressure
inadequate water/brine cooler and condenser flow
high, low, or loss of voltage
ground fault
voltage imbalance
current imbalance
excessive motor acceleration time
excessive starter transition time
lack of motor current signal
excessive motor amps
excessive compressor surge
temperature and transducer faults
*Superheat is the difference between saturation temperature
and sensible temperature. The high discharge temperature
safety measures only sensible temperature.
Starter faults or optional protective devices within the starter
can shut down the chiller. The protective devices you have for
your application depend on what options were purchased.
If the PIC II control initiates a safety shutdown, it displays
the reason for the shutdown (the fault) on the CVC/ICVC dis-
play screen along with a primary and secondary message, ener-
gizes an alarm relay in the starter, and blinks the alarm light on
the control panel. The alarm is stored in memory and can be
viewed on the ALARM HISTORY and ISM_HIST screens on
the CVC/ICVC, along with a message for troubleshooting. If
the safety shutdown was also initiated by a fault detected in the
motor starter, the conditions at the time of the fault will be
stored in ISM_HIST.
To give more precise information or warnings on the
chillers operating condition, the operator can define alert lim-
its on various monitored inputs. Safety contact and alert limits
are defined in Table 3. Alarm and alert messages are listed in
the Troubleshooting Guide section, page 76.
If compressor motor overload occurs, check the motor for
grounded or open phases before attempting a restart.