Carrier XRV Refrigerator User Manual


 
CL-10
19XR, XRV PIC II RAMP_DEM TABLE CONFIGURATION SHEET
19XR, XRV PIC II TEMP_CTL TABLE CONFIGURATION SHEET
DESCRIPTION RANGE UNITS DEFAULT VALUE
Pulldown Ramp Type:
Select: Temp=0, Load=1
0/1 1
Demand Limit + kW Ramp
Demand Limit Source
Select: Amps=0, kW=1
0/1 0
Motor Load Ramp% Min 5 to 20 10
Demand Limit Prop Band 3 to 15 % 10
Demand Limit At 20 mA 40 to 100 % 40
20 mA Demand Limit Opt 0/1 DSABLE/ENABLE DSABLE
Motor Rated Kilowatts 50 to 9999 kW 145
Demand Watts Interval 5 to 60 MIN 15
DESCRIPTION RANGE UNITS DEFAULT VALUE
Control Point
ECW Control Option 0/1 DSABLE/ENABLE DSABLE
Temp Pulldown Deg/Min 2 to 10 ˆF3
Temperature Reset
RESET TYPE 1
Degrees Reset At 20 mA 30 to 30 ˆF10
RESET TYPE 2
Remote Temp -> No Reset 40 to 245 DEG F 85
Remote Temp -> Full Reset 40 to 245 DEG F 65
Degrees Reset 30 to 30 ˆF10
RESET TYPE 3
CHW Delta T -> No Reset 0 to 15 ˆF10
CHW Delta T -> Full Reset 0 to 15 ˆF0
Degrees Reset 30 to 30 ˆF5
Select/Enable Reset Type 0 to 3 0