Carrier 69NT40-521 Refrigerator User Manual


 
3-12T-268-07
CODE
#
DESCRIPTIONTITLE
AL53
NiCad Battery Pack
Failure
Alarm 53 is caused by the nicad battery pack being too low of a charge for
battery-backed recording.
NOTE
Check for recharging or replacing battery pack.
AL54
Primary Supply Air
Sensor Failure
(STS)
Alarm 54 is activated by an invalid primary supply sensor reading that is sensed
outside the range of --50 to +70_C(--58_F to +158_F) or if the probe check logic
has determined there is a fault with this sensor. If Alarm 54 is activated and the
primary supply is the control sensor, the secondary supply sensor will be used for
control if the unit is so equipped. If the unit does not have a secondary supply
probe, and AL54 is activated, the (primary return sensor, minus 2_C) will be used
for control.
NOTE
The P5 Pre-Trip test must be run to inactivate the alarm (refer to section 3.2.1).
AL55
DataCORDER
Failure
This alarm has been activated to indicate the DataCORDER has been disabled
due to internal failure. To clear this alarm, simply reconfigure the unit to its OEM
model number by using the multi-configuration card.
AL56
Primary Return Air
Sensor Failure
(RTS)
Alarm 56 is activated by an invalid primary return sensor reading that is outside
the range of --50 to +70_C(--58_F to +158_F). If Alarm 56 is activated and the
primary return is the control sensor, the secondary return sensor will be used for
control if the unit is so equipped. If the unit is not equipped with a secondary
return sensor or it fails, the primary supply sensor will be used for control.
NOTE
The P5 Pre-Trip test must be run to inactivate the alarm (refer to section 3.2.1).
AL57
Ambient
Temperature Sensor
Failure (AMBS)
Alarm 57 is triggered by an ambient temperature reading outside the valid range
from --50_C(--58_F) to +70_C (+158_F).
AL58
Compressor High
Pressure Safety
(HPS)
Alarm 58 is triggered when the compressor high discharge pressure safety switch
(HPS) remains open for at least one minute. This alarm will remain active until the
pressure switch resets, at which time the compressor will restart.
AL59
Heat Termination
Thermostat (HTT)
Safety
Alarm 59 is triggered by the opening of the heat termination thermostat (HTT) and
will result in the disabling of the heater. This alarm will remain active until the
thermostat resets.
AL60
Defrost Termination
Sensor Failure
(DTS)
Alarm 60 is an indication of a probable failure of the defrost termination sensor
(DTS). It is triggered by the opening of the heat termination thermostat (HTT) or
the failure of the DTS to go above 25.6_C(78_F) within two hours of defrost
initiation. After one-half hour with a frozen range set point, or one-half hour of
continuous compressor run time, if the return air falls below 7_C(45_F), the
Controller checks to ensure defrost termination sensor (DTS) has dropped to
10_C or below. If not, a DTS failure alarm is given and the defrost mode is
operated off of return temperature sensor (RTS). The defrost mode will be
terminated after one hour by the Controller.
AL61 Heaters Failure
Alarm 61 is the heater alarm caused by detection of improper amperage resulting
from heater activation (deactivation). Each phase of the power source is checked
for proper amperage.This alarm is a display alarm with no resulting failure action,
and will be reset by a proper amp draw of the heater.
AL62
Compressor Circuit
Failure
Alarm 62 is triggered by improper current draw increase (or decrease) resulting
from compressor turn on (or off). The compressor is expected to draw a minimum
of 2 amps; failure to do so will activate the alarm.This is a display alarm with no
associated failure action and will be reset by a proper amp draw of the
compressor.