Emerson E2 Refrigerator User Manual


 
10-16E2 RX/BX/CX I&O Manual 026-1614 Rev 4 5-JAN-2013
work Status screen (See Figure 10-24). The Network
Summary screen displays information such as the Subnet
and Node addresses
for each board, and the status of Eche-
lon and I/O boards.
To get to the Network Summary Screen:
1. Press
to open the Main Menu
2. Press
(System Configuration)
3. Press
(Network Setup)
4. Press
(Network Summary)
From the Network Summary screen you can see the
tot
al (E2) devices online or offline, status, setup screens,
change board or controller names, configure and commis-
sion devices, delete a device, and
view detailed status
screens of controllers.
After determining if a board is offline, turn to Appen-
dix E: Troubleshooting.
10.14 Set Up Echelon
Network
10.14.1 Specifying Number of
Devices
To specify the number of devices on the Echelon Net-
work, navigate to the Connected I/O screen:
1. Press
to open the Main Menu
2. Press
(System Configuration)
3. Press
(Network Setup)
4. Press
(Connected I/O Boards & Controllers)
Figure 10-25
- Connected I/O Screen (RX version shown)
After logging in for the first time, the Connected I/O
screen will ask you to specify how many of each type of
device will be connected to the E2 you are currently pro-
gramming. (Options will vary depending on the type of
co
ntroller used.)
Unit Number (Eche
lon Subnet) Each E2 on the
Echelon Network must have a different unit number.
This can be any number from 1 to 255, but each E2’s
number must be unique. No two E2s on the network
may have the same unit number.
Enter this number in the Unit Number field. It is rec-
ommended you number the first E2 “1” and number
th
e other E2s on the network sequentially (2, 3, 4,
etc.).
Unit Name Type a name for the E2 in the Unit
Name field
.
Unit Controllers (Echelon)
Liquid Ctrls (CC100P/CC100LS) Enter the com-
bined number of pulse valve case controllers
(C
C100Ps) and liquid-side stepper valve case con-
trollers (CC100LSs) in this field.
Suction Controllers (CC100H) Enter the num-
ber of suction stepper case controllers (CC100Hs) in
th
is field.
Circuit Suction (CS100) Enter the number of suc-
tion lineup circuit controllers (CS100s) in this field.
ESR8 Line Up Boards Enter the number of ESR
sucti
on lineup circuit boards (SR100s) in this field.
TD3 Temperature Displays Enter the number of
TD3 tem
perature display units in this field.
EC2- 29x Case Controllers Enter the number of
EC2-29x refrigerated case con
trollers in this field.
EC2-39x Case Controllers Enter the number of
EC2-39x refrigerated case con
trollers in this field.
Echelon 16AI Enter the number of 16AIe analog
in
put boards in this field.
Echelon 8RO Enter the number of 8ROe analog
in
put boards in this field.
10.14.2 Commissioning a Device
Once all records have been created and defined for all
devices on the Echelon Network, they must be “commis-
sioned.” Commissioning is necess
ary for the E2 to identify
and establish communications with all devices on the net-
work.
To start commissioning, open the Network Summary
screen:
1. Press
to open the Main Menu