11-46 • E2 RX/BX/CX I&O Manual 026-1614 Rev 4 5-JAN-2013
power monitoring inputs will appear under the Inputs tab
of the application. All inputs must be connected to board
and points set up with Engineering Units of Amps.
11.16 Anti-Sweat Setup
An anti-sweat application controls one anti-sweat
zone. An anti-sweat zone is defined as one or more anti-
sweat heaters that use the same dewpoint (or RH and tem-
perature) sensors and the same control setpoints. If all the
out
puts on a 20-channel PMAC panel are going to use the
same setpoints and dewpoint device(s), then all the heaters
may be set up in a single zone.
Zones are set up in a single screen called the Anti-
Sweat
Control Setup screen.
11.16.1 How Anti-Sweat Works
Anti-sweat applications control anti-sweat heaters by
monitoring the dewpoint. A dewpoint value may come
from a dewpoint probe mounted within the Zone, or it may
be calculated automatically by the E2 using a combination
of a relative humidity sensor and a temperature sensor.
The dewpoint value is used to pulse the heaters ON for
a certain percentage of
a user-defined time interval. The
dewpoint is compared to the anti-sweat application’s con-
trol setpoints (the Full ON Dewpoint and the Full OFF
Dewp
oint). Based on this comparison, the anti-sweat heat-
ers will do one of three things:
• If the dewpoint is equal to or above the Full ON
Dewp
oint, the heaters remain ON 100% of the time.
• If the dewpoint is equal to or below the Full OFF
Dewpoint, the
heaters will be ON 0% of the time
(fully OFF).
• If the dewpoint is between the Full ON and Full
OFF Dewpoint, the heaters
will be pulsed ON for a
percentage of the specified time interval. The per-
centage is determined by proportionately measuring
where the
dewpoint falls between the range of val-
ues formed by the two setpoints.
Figure 11-6 shows an example of an anti-sweat appli-
cation. The setpoints (Full ON = 80°F, Full OFF = 20°F)
fo
rm the range of dewpoints across which the heaters will
be pulsed. When the measured dewpoint is 45°F (directly
in between both setpoints), the percentage will be 50%,
and the heaters will be pulsed ON for five seconds of the
defined 10-second interval. If the dewpoint drops to 30°F,
the percentage will lower to 20%, and the heaters will be
on only two seconds out of every 10.
11.17 Heat/Cool Control
Heat/Cool Control is a special kind of sensor control
that applies to heating and cooling devices. Heat/Cool
Control applications use PID control to vary the amount of
heating and cooling based on the current temperature and
its relation to the heating or cooling setpoint. Both staged
and modulated (0-100%) heating and cooling outputs are
supported by Heat/Cool Control.
Heat/Cool controls are availab
le in RX units, allowing
small installations with simple HVAC systems to use one
controller for all refrigeration and HVAC systems.
11.17.1 Temperature Control
Heat/Cool applications use PID control to vary the out-
put of heating and cooling devices.
As is the case with all
applications that use PID control, Heat/Cool control
makes use of a PID setpoint and a throttling range. Refer
to Appendix D: PID Control for more information.
Unlike normal PID loops that assume a 50% output is
required to keep the temperature stabilize
d on the setpoint,
Heat/Cools strive to stabilize the temperature on the set-
point with the output at 0%. Thus, when the temperature
go
es below a heating setpoint or above a cooling setpoint,
the heating or cooling outputs climb from 0% to 100% as
determined by the throttling range (see Figure 11-25).
Figure 11-25
- Example of Heat/Cool PID Control
Lighting Control Command Cells
Input Value
1 - 4
In 1
In 2
In 3
In 4
Use Alt Comb
Out
DVCOMBINER
SCHEDIF
Out
Comb Type
Alt Comb
Invert Output
Alt Combiner
DV
Logic In
Sched In
Use Alt Sch
Occupied
DV
Comb Type
Alt Comb
Invert Output
MIN ON/OFF
In Out
ONESHOT
Trigger
Out
In
Out
OVERRIDE
Command
(on, off, normal)
Type
(timed, fixed)
OV time
Pulse Width
Timer
Alt Schedule
DV
DV
Min On/Off Times
Min On/Off Delays
LIGHTS
26512043
By default, only the proportional and integral modes of
PID control are enabled for Heat/Cools. The user may
choose to add the Derivative mode or to get rid of the Inte-
gral mode and use strictly Proportional control.