Emerson E2 Refrigerator User Manual


 
D-6E2 RX/BX/CX I&O Manual 026-1614 Rev 4 5-JAN-2013
are 20% and 100% respectively, the output per-
centage will never be below 20%, even if the P, I,
and D Mode adjustments call for the output to be
below 20%. The output will remain in saturation
at 20% until a higher output percentage is called
for.
In short, PID works as it normally does, except the out-
put never goes below Output at Minimum or above Output
at Maximum.
Minimum Accumulated Error
The Minimum Accumulated Error setting disables
error accumulation in the “I” Mode when the current error
is equal to or less than a certain amount. For example, if
the PID setpoint is 30 and the Minimum Accumulated
Error is 1, the “I” Mode will not adjust the PID output per
-
centage as long as the input is between 29 and 31.
Because “I” Mode does not accumulate error within
the Minimum Accumulated Error range, the control input
is allowed to settle on a value other than the setpoint. It is
possible in the example given above for the system to
achieve stability at any value between 29 and 31 without
the “I” Mode trying to bring the error to zero.
Application
The practical use of Minimum Accumulated Error is to
set up a “close enough” zone around your PID setpoint.
When the control input is within the zone, PID will not
worry about making any “I” adjustments to attempt to
equalize the input and the setpoint. Proportional Mode will
handle any minor input changes that occur within this
zone.
Filtering
Filtering is a feature commonly used by CC-100s in
valve control (and it thus sometimes called “valve filter
-
ing”). The primary purpose of filtering is to dampen the
rate of change of the PID percentage in an effort to make
the PID control loop less reactive.
The filtering feature takes samples of the PID output
percentage at regular intervals (which are determined by a
parameter called the filter period). Every time a new filter
period interval occurs, the PID percentage sampled during
the last period interval is subtracted from the current PID
percentage from the current period interval.
The result of this subtraction is multiplied by a param-
eter called the filter percentage (0 - 100%) to yield the
actual amount the PID percentage will change.
Over time, the application of the filter percentage to
the change in PID position will result in a PID control loop
with a smaller amount of reaction to changes in the input.
Example: A stepper EEV valve on a CC-100 is con-
trolled by PID control. Valve filtering is active in this CC-
100, with the filter period set to six seconds and the filter
percentage set to 75%.
During one sample taken during a period interval, the
CC-100 calls for a valve position of 50%. One period (six
seconds) later, the CC-100 asks for a 58% valve opening.
The total difference between the current sample and
the previous sample is +8% (58 - 50%). To determine the
actual amount the valve will change, the CC-100 multi
-
plies the filter percentage (75%) with the total amount of
valve position change (8%). As a final result, the new PID
output value for the CC-100 will be 56%.
Note that filtering only slows down the reaction of the
PID loop. When the control input is stabilized, the PID
loop will eventually achieve the output percentage it is
calling for.
To demonstrate this, suppose in the example above the
CC-100 continues to call for a 58% output during the
period immediately after the 6% adjustment. Since the
total difference between the asked-for percentage and the
current actual percentage is 2% (58 - 56), valve filtering
will make the new adjustment for that period 1.5% (75%
of 2). As a result, the new valve output would be 57.5%.
Future filter periods will bring the actual output even
closer to the asked-for output.
Application
PID filtering is used for systems that appear to be over-
reacting to changes in the control input. If filtering is to be
used at all, it is recommended to use caution, since even a
small amount of filtering may cause the PID loop to
become
underreactive.