Emerson E2 Freezer User Manual


 
10-22E2 RX/BX/CX I&O Manual 026-1610 Rev 13 14-SEP-2011
10.16.1 Specifying Alarm Reporting
Types
Apart from storing alarms it generates in its own
Alarm Advisory Log, E2 can also report alarms it gener-
ates or receives in order to notify personnel. E2 can report
alarms in several different ways.
10.16.1.1 The Display Line
Alarms that occur within an E2 (or which are received
by an Alarm Annunciator from another E2) may be
reported to the header display at the top of the screen.
When an alarm is reported to the display, the word
“*ALARM*” flashes underneath the time at the top of the
screen, allowing site managers or supervisors to see that
one or more alarms are active for the E2.
10.16.1.2 The Alarm Output
Each E2 has a single digital output that reacts to alarm
reports. An alarm can be reported to this output, in which
case the output turns ON and remains on until the alarm
condition has returned to normal.
10.16.1.3 Dial-Out
Alarms may be sent to remote alarm receivers via the
modem defined for the controller. Possible dial-out
devices include a PC running UltraSite, a printer, a fax
machine, and a digital pager. Dial-out sites are configured
in Section 10.16.3.
10.16.1.4 The Echelon Network (The
Alarm Annunciator)
If multiple E2s exist on a network, you may choose to
send alarms from all E2s across the Echelon Network so
that they may be picked up by the Alarm Annunciator.
The Alarm Annunciator is the primary alarm reporting
device in a multiple-device E2 Network. The Alarm
Annunciator gathers all alarms posted by all devices on the
Echelon Network, records them in its own advisory log,
and applies its own set of alarm filters to determine if the
alarms should be dialed out, reported to its display, or sent
to its Advisory Output.
There are several benefits to having an Alarm Annun-
ciator:
An Alarm Annunciator makes it possible to handle
all alarm dial-outs for all controllers with a single
modem or network card.
Users can view alarm notifications and alarm logs
for all controllers from the Alarm Annunciator.
Only the Alarm Annunciator needs to be pro-
grammed with alarm filter settings for dial-out, out-
put, and display. All other controllers may be
programmed to simply send all alarms to the Alarm
Master via the LonWorks Network.
10.16.2 Setting up an E2 to be an
Alarm Annunciator
Any E2 on the network that has a modem or Ethernet
connection can be set up as an alarm annunciator, but only
one alarm annunciator per network is allowed. To set up
from the Main Menu:
1. Press
(System Configuration)
2. Press
(System Information)
3. Press
(General Controller Info)
4. Set Alarm Annunc field to Yes.
Figure 10-38
- Display Line
NOTE: When the E2 is set up as an Alarm An-
nunciator, the Home screen becomes the
Alarm Log.
Figure 10-39
- Alarm Annunciator