Emerson E2 Freezer User Manual


 
Ethernet IP Configurations E2 Ethernet Peer Communications7-1
7 E2 Ethernet Peer Communications
Communication between E2 controller version 2.10 or
greater may now be implemented through an Ethernet net-
work using TCP/IP protocol. To utilize peer connections
over Ethernet, the following tasks must be performed:
Upgrade the E2 controller firmware to version 2.10
or greater.
Install an industry-standard Ethernet switch(es) or
hub(s) in an area or areas nearby the E2 controllers.
Install Ethernet straight-through cabling at the site
from each E2 to the switch or hub. Installation of
RJ-45 connectors may be necessary to achieve this
goal. The recommended cabling is CAT 5.
7.1 Ethernet IP Configura-
tions
If using an open network configuration (see Section
7.4.2, Open Network Layout), contact your IT Network
Administrator for all IP configuration information (IP
Address, Subnet Mask, Primary and Default Gateway set-
tings).
7.2 Hardware Specifica-
tions
Standard industry-accepted practices for wiring of Eth-
ernet networks are expected. E2 controllers use a star
topology, identical to PC deployment. This includes a
unique “point-to-point” run from a switch or hub to the
controller (see Table 7-1 for hub part numbers for order-
ing). This is done with Category5 (or better) cable. Maxi-
mum distance for a run of 10BaseT is 328 feet (100
meters) (11.5 dB loss max).
The maximum number of controllers allowed on an
IP subnet is 20. All E2 controllers that must com-
municate with each other must be on the same sub-
net.
Recommended Ethernet cabling is CAT 5 (straight-
through cable).
328 feet (100 meters) is the maximum distance
allowed between devices before a switch or hub
must be added.
7.2.1 Components
Equipment
Type
Specifications
Ethernet Five- or
Nine-port Switch
(may require an
additional power
supply)
* Industrial grade
* Operating/storage temp range:
-40°F to 185°F
* Vibration: IEC68-2-6
* RH: 5 to 95%
* UL 508A, CE approved
* Supports 10Base-T crossover
cable
* Supports all IEEE 802.3 proto-
col
* Supports Auto Crossover
MDI/MDI-X
* Screw-terminal power connec-
tors
Ethernet Surge
and Lightning
Protector (recom-
mended)
* Industrial grade
* Surge capacity: 1 kA / line
*Operating temp range: -40°F to
185°F
*Max frequency: 155 MHz
*Clamp and rated: 10V and 5V
10-Base-T/100-
Base-TX Hub
Room Temperature (0 to 50 C)
P/N 570-0100
10-Base-T/100-
Base-TX Hub
Extended Temperature
(-40 to 65 C) P/N 570-0200
Table 7-1
- Equipment for E2 Ethernet Peer Communications
NOTE: An external power supply may be
needed.