Application Setpoint Has Changed 99 A user has changed a setpoint in one of E2’s applica-
tions.
Application Was Created 99 A user has created a new application in this E2.
Application Was Deleted 99 A user has deleted an existing application in this E2.
ARTC/MultiFlex RTU Override
Switch Stuck
20 An override switch on an ARTC/ MultiFlex RTU has
been ON for a prolonged period of time, suggesting a
possible switch failure.
ARTC/MultiFlex RTU Reset From
Power Failure
50 An ARTC/MultiFlex RTU lost power and reset when
power was restored.
Attempt To Write Past Mem. EOB 50 The E2 attempted to write data to memory, but the
memory was full.
Average Log Stuck-No Memory 15 The Average Log cannot be written because there is
not enough memory.
Bad Modem 20 The modem on this E2 is not functioning properly.
Battery backed memory lost 30 Battery backed memory loss not due to cleanout.
Batt Runtime Limit 99 Battery runtime has exceeded 80% of the battery life-
time.
Binding Input To Output Failed 20 A valid connection could not be made between an
input and an output.
BIOS/BIOS Ext. Update Failed 20 An update to the E2’s BIOS has failed.
BIOS/BIOS Extension Updated 50 The E2’s BIOS was successfully updated.
Can't Set Hardware Clock 20 The E2 is unable to change the time on its hardware
clock.
Case Cleaning Was Started User A case circuit has entered clean mode.
Case Temp Hi Limit Exceeded User A single temperature sensor in a Standard Circuit or
Case Control Circuit is recording a temperature
higher than its defined case temperature high set-
point.
Case Temp Low Limit Exceeded User A single temperature sensor in a Standard Circuit or
Case Control Circuit is recording a temperature lower
than its defined case temperature low setpoint.
Cell Config Not Restored 15 E2’s attempt to restore configuration data to its appli-
cations has failed.
Cell Create Failed For Restore 20 E2 attempted to create new applications as part of the
configuration restoration process and failed to do so
successfully.
Checkit Sensor Has Failed User A Checkit sensor is returning an invalid temperature
value, indicating a sensor failure.
Checkit Sensor Is Alarming User A Checkit sensor on a Suction Group application is
recording a high temperature.
Checkit Sensor Is In Notice User A Checkit sensor’s temperature is above its pro-
grammed notice setpoint.