Mitsubishi Electronics SW2D5C-GTWK2-E Frozen Dessert Maker User Manual


 
8 - 19
8.6 Error Code and Error Message List
8.6.1 GOT error code list
582
Cannot generate
Advanced recipe file.
Cannot generate advanced recipe file. Confirm the following
and execute recipe processing again.
1. Confirm whether the memory card is installed.
2.
Confirm whether the CF card access switch of the GOT is
ON.
3. Confirm the available memory of the memory card.
583
Unable to save device
value to Advanced recipe
file.
Unable to save device value to advanced recipe file.
1. Confirm the write-protection of memory card.
2.
Confirm whether the attribute of saving file is for reading
only.
584
Advance recipe file save
error
An error has occurred during the advanced recipe file writing.
Do not pull the memory card out while the Advanced Recipe
is operating.
585
Advanced recipe file
upload error
An error has occurred during the advanced recipe file reading.
Do not pull the memory card out while the Advanced Recipe
is operating.
586
Specified Advanced
recipe number does not
exist.
The advanced recipe of non-existing number is about to be
executed.
Execute advanced recipe of existing number.
587
Specified record number
does not exist.
The advanced record of non-existing number is about to be
executed.
Execute record of existing number.
588
Cannot save recipe data
to read only record.
Saving recipe is about to be executed to the record of which
recipe device value cannot be edited.
Make the recipe device value of the record editable with
Advanced Recipe Setting of GT Designer2 or specify the
record of which recipe device value can be edited.
589
Recipe device save error.
Recipe file does not exist.
Saving recipe is about to be executed to the advanced recipe
setting that is set for not using file.
Specify the advanced recipe setting that uses file.
590
Recipe device upload
error. Recipe device value
does not exist.
Loading recipe is about be executed to the record of which
recipe device value is not set.
Specify the record of which recipe device value is set.
591
Advanced Recipe error.
Check recipe data.
The advanced recipe setting is not correct.
Confirm the advanced recipe setting of the project data and
download it to the GOT again.
595 Logging file error.
Logging file error.
When collecting data again, delete logging files and
management files.
596
Logging setting does not
exist or setting value
error.
The logging setting specified in the historical trend graph
setting does not exist.
Review the historical trend graph setting and specify a logging
setting that exists.
600
Unsupported version of
printer unit.
The version of OS installed in the GOT is not compatible with
the printer unit.
Install the extended function OS (Printer) with the latest GT
Designer2.
Error
code
Error message Action
Channel
No.
storage