Carrier 30XW150-400 Refrigerator User Manual


 
102
APPENDIX A — TOUCH PILOT™ DISPLAY TABLES (cont)
LEGEND
TOUCH PILOT DESCRIPTION
TOUCH PILOT
POINT NAME
TOUCH PILOT PATH LINE
READ/
WRITE
CCN TABLE NAME
Reclaim Deadband hr_deadb MAIN MENU\Setpoint\SETPOINT 37 RW Setpoint Configuration Tables\SETPOINT
Reclaim Entering Fluid HR_EWT MAIN MENU\Status\RECLAIM 5 RO Status Display Tables\RECLAIM
Reclaim Fluid Setpoint RSP MAIN MENU\Status\RECLAIM 7 RO Status Display Tables\RECLAIM
Reclaim Leaving Fluid HR_LWT MAIN MENU\Status\RECLAIM 6 RO Status Display Tables\RECLAIM
Reclaim NRCP2 Board REC_NRCP MAIN MENU\Maint\BOARD_PN 10 RO Maintenance Display Tables\BOARD_PN
Reclaim Setpoint rsp MAIN MENU\Setpoint\SETPOINT 36 RW Setpoint Configuration Tables\SETPOINT
Reclaim Status Circuit A hrstat_a MAIN MENU\Status\RECLAIM 10 RO Status Display Tables\RECLAIM
Reclaim Status Circuit B hrstat_b MAIN MENU\Status\RECLAIM 20 RO Status Display Tables\RECLAIM
Reclaim Valve Position hr_v_pos MAIN MENU\Status\RECLAIM 8 RO Status Display Tables\RECLAIM
Reference Number RefNum MAIN MENU\Config\Ctlr-ID 6 RO Configuration Tables\!CtlrID\PD5_XAXQ
Refrigerant Charge Ctrl charge_c MAIN MENU\Service\MAINTCFG 3 RW Service Configuration Tables\MAINTCFG
Remote Heat/Cool Switch HC_SW MAIN MENU\Status\STATEGEN 3 RO Status Display Tables\STATEGEN
Remote Interlock Status REM_LOCK MAIN MENU\Status\STATEGEN 15 RO Status Display Tables\STATEGEN
Remote Reclaim Switch RECL_SW MAIN MENU\Status\STATEGEN 5 RO Status Display Tables\STATEGEN
Remote Setpoint Switch SETP_SW MAIN MENU\Status\STATEGEN 7 RO Status Display Tables\STATEGEN
Requested Electric Stage eh_stage MAIN MENU\Maint\LOADFACT 23 RO Maintenance Display Tables\LOADFACT
Reset Amount reset MAIN MENU\Maint\LOADFACT 6 RO Maintenance Display Tables\LOADFACT
Reset in Effect Mode_03 MAIN MENU\Status\MODES 4 RO Status Display Tables\MODES
Reset Maintenance Alert S_RESET MAIN MENU\Maint\SERMAINT 1 RO Maintenance Display Tables\SERMAINT
Reset/Setpnt 4-20mA Sgnl SP_RESET MAIN MENU\Status\STATEGEN 41 RO Status Display Tables\STATEGEN
Reverse Alarms Relay al_rever MAIN MENU\Config\USER 43 RW Configuration Tables\USER
Rotate Condenser Pumps? ROTHPUMP MAIN MENU\Status\STATEGEN 25 RO Status Display Tables\STATEGEN
Rotate Cooler Pumps? ROTCPUMP MAIN MENU\Status\STATEGEN 22 RO Status Display Tables\STATEGEN
Run Status STATUS MAIN MENU\Status\GENUNIT 4 RO Status Display Tables\GENUNIT
Running Status RUNNING MAIN MENU\Status\STATEGEN 31 RO Status Display Tables\STATEGEN
Reference Delta
Circuit A delt_r_a MAIN MENU\Maint\DEFROSTM 12 RO Maintenance Display Tables\DEFROSTM
Circuit B delt_r_b MAIN MENU\Maint\DEFROSTM 29 RO Maintenance Display Tables\DEFROSTM
Refrigerant Pump Out
Circuit A FC_PMP_A MAIN MENU\Status\FREECOOL 16 RO Status Display Tables\FREECOOL
Circuit B FC_PMP_B MAIN MENU\Status\FREECOOL 26 RO Status Display Tables\FREECOOL
Circuit C FC_PMP_C MAIN MENU\Status\FREECOOL 36 RO Status Display Tables\FREECOOL
Running Output
Circuit A Q_RUN_A MAIN MENU\Status\QCK_TST1 43 RW Status Display Tables\QCK_TST1
Circuit B Q_RUN_B MAIN MENU\Status\QCK_TST1 44 RW Status Display Tables\QCK_TST1
Circuit C Q_RUN_C MAIN MENU\Status\QCK_TST1 45 RW Status Display Tables\QCK_TST1
Saturated Condensing Tmp
Circuit A SCT_A MAIN MENU\Status\CIRCA_AN 12 RO Status Display Tables\CIRCA_AN
Circuit B SCT_B MAIN MENU\Status\CIRCB_AN 12 RO Status Display Tables\CIRCB_AN
Circuit C SCT_C MAIN MENU\Status\CIRCC_AN 12 RO Status Display Tables\CIRCC_AN
Saturated Suction Temp
Circuit A SST_A MAIN MENU\Status\CIRCA_AN 13 RO Status Display Tables\CIRCA_AN
Circuit B SST_B MAIN MENU\Status\CIRCB_AN 13 RO Status Display Tables\CIRCB_AN
Circuit C SST_C MAIN MENU\Status\CIRCC_AN 13 RO Status Display Tables\CIRCC_AN
Circuit C Q_SLI_1C MAIN MENU\Status\QCK_TST1 31 RW Status Display Tables\QCK_TST1
RO Read Only