Carrier 30XW150-400 Refrigerator User Manual


 
CL-5
Record Configuration Information
*Not supported.
TOUCH PILOT™
DESCRIPTION
NAVIGATOR
ITEM
NAVIGATOR™
SUBMODE
RANGE DEFAULT ENTRY
Cooling Setpoint 1 CSP.1 Set Point COOL XXX.X 44.0° F
Cooling Setpoint 2 CSP.2 Set Point COOL XXX.X 44.0° F
Cooling Ice Setpoint CSP.3 Set Point COOL XXX.X 44.0° F
Current No Reset Value (Cooling) CRV1 Set Point COOL XXX.X 0
Current Full Reset Value (Cooling) CRV2 Set Point COOL XXX.X 0
Delta T No Reset Value (Cooling) CRT1 Set Point COOL XXX.X 0
Delta T Full Reset Value (Cooling) CRT2 Set Point COOL XXX.X 0
OAT No Reset Value (Cooling) CRO1 Set Point COOL XXX.X 14.0° F
OAT Full Reset Value (Cooling) CRO2 Set Point COOL XXX.X 14.0° F
Space T No Reset Value CRS1 Set Point COOL XXX.X 14.0° F
Space T Full Reset Value CRS2 Set Point COOL XXX.X 14.0° F
Cooling Reset Deg. Value DGRC Set Point COOL XX.X 0
Cool Changeover Setpoint CAUT Set Point COOL XXX.X 75° F
Cooling Ramp Loading CRMP Set Point COOL X.X 1.0
Heating Setpoint 1 HSP.1 Set Point HEAT XXX.X 100.0° F
Heating Setpoint 2 HSP.2 Set Point HEAT XXX.X 100.0° F
Current No Reset Value (Heating) HRV1 Set Point HEAT XXX.X 0
Current Full Reset Value (Heating) HRV2 Set Point HEAT XXX.X 0
Delta T No Reset Value (Heating) HRT1 Set Point HEAT XXX.X 0
Delta T Full Reset Value (Heating) HRT2 Set Point HEAT XXX.X 0
OAT No Reset Value (Heating) HRO1 Set Point HEAT XXX.X 14.0° F
OAT Full Reset Value (Heating) HRO2 Set Point HEAT XXX.X 14.0° F
Heating Reset Deg. Value DGRH Set Point HEAT XX.X 0
Heating Changeover Setpoint HAUT Set Point HEAT XX.X 64.0° F
Heat Ramp Loading HRMP Set Point HEAT X.X 1.0
Switch Limit Setpoint 1 DLS1 Set Point MISC XXX 100
Switch Limit Setpoint 2 DLS2 Set Point MISC XXX 100
Switch Limit Setpoint 3 DLS3 Set Point MISC XXX 100
Water Val Condensing Stp W.SCT Set Point MISC XXX.X 95.0° F
None (I/O Button) OPER Operating Modes SLCT X
Setpoint Select SP.SE Operating Modes SLCT X
Heal/Cool Select HC.SE Operating Modes SLCT X COOLING