APPENDIX B — NAVIGATOR™ DISPLAY TABLES
MODE — RUN STATUS
*As data in all of these categories can exceed 9999 the following display strategy is used:
From 0-9999 display as 4 digits.
From 9999-99999 display xx.xK
From 99900-999999 display as xxxK.
ITEM EXPANSION UNITS RANGE COMMENT
WRITE
STATUS
CCN TABLE CCN POINT
PAGE
NO.
VIEW AUTO DISPLAY
EWT Entering Fluid Temp XXXX.X
(deg F/deg C)
0-100 STATEGEN COOL_EWT 44
LWT Leaving Fluid Temp XXX.X
(deg F/deg C)
0-100 STATEGEN COOL_LWT 44
SETP Active Setpoint XXX.X
(deg F/deg C)
0-100 GENUNIT SP 35, 55
CTPT Control Point XXX.X
(deg F/deg C)
0-100 GENUNIT CTRL_PNT 35
STAT Unit Run Status Off
Running
Stopping
Delay
GENUNIT STATUS 22-25
OCC Occupied NO/YES GENUNIT CHIL_OCC 22-25
CTRL Status Unit Control Type Local Off
Local On
CCN
Remote
GENUNIT ctr_type 22-25
CAP Percent Total Capacity XXX (%) 0-100 GENUNIT CAP_T
CAP. A Percent Capacity Cir A XXX (%) 0-100 GENUNIT CAPA_T
CAP. B Percent Capacity Cir B XXX (%) 0-100 GENUNIT CAPB_T
CAP. C Percent Capacity Cir C XXX (%) 0-100 GENUNIT CAPC_T
CAP. S Capacity Indicator XX 0-32 MAINT OVER_CAP 43
LIM Active Demand Limit Val XXX (%) 0-100 GENUNIT DEM-LIM
CURR Actual Chiller Current XXX (amps) 0-4000 GENUNIT TOT_CURR
CUR.L Chiller Current Limit XXX (amps) 0-4000 GENUNIT CURR_LIM
ALRM Alarm State 0=Normal
1=Partial
2=Shutdown
GENUNIT ALM 68
EMGY Emergency Stop DSBL/ENBL GENUNIT EMSTOP
CH.SS CCN Chiller Start Stop DSBL/ENBL GENUNIT CHILL_S_S
HC.ST Heat Cool Status 0=Cooling
1=Heating
2=Standby
Heating and
Standby not
supported.
GENUNIT HEATCOOL 45
RC.ST Reclaim Select Status NO/YES Not supported. GENUNIT reclaim_sel
TIME Time of Day XX.XX 00:00-23:59 N/A TIME
MNTH Month of Year 1=January
2=February
3=March
4=April
6=May
6=June
7=July
8=August
9=September
10=October
11=November
12=December
N/A moy
DATE Day of Month XX 1-31 N/A dom
YEAR Year of Century XX 00-99 N/A yoc
RUN MACHINE STARTS/HOURS
HRS.U Machine Operating Hours XXXX (hours) 0-999000* forcible hr_mach
STR.U Machine Starts XXXX 0-9999* forcible STRTHOUR st_mach
HR.P1
Water Pump 1 Run Hours XXXX (hours) 0-999000* Not supported. forcible FANHOURS hr_cpum1
HR.P2 Water Pump 2 Run Hours XXXX (hours) 0-999000* Not supported. forcible FANHOURS hr_cpum2
HR.P3 Condenser Pump 1 Hours XXXX (hours) 0-999999* Not supported. forcible FANHOURS hr_hpump1
HOUR COMPRESSOR RUN HOURS
HR.A Compressor A Run Hours XXXX (hours) 0-999000* forcible STRTHOUR hr_cp_a
HR.B Compressor B Run Hours XXXX (hours) 0-999000* forcible STRTHOUR hr_cp_b
HR.C Compressor C Run Hours XXXX (hours) 0-999000* forcible STRTHOUR hr_cp_c
STRT COMPRESSOR STARTS
ST.A Compressor A Starts XXXX 0-999000* forcible STRTHOUR st_cp_a
ST.B Compressor B Starts XXXX 0-999000* forcible STRTHOUR st_cp_b
ST.C Compressor C Starts XXXX 0-999000* forcible STRTHOUR st_cp_c