APPENDIX C — CCN TABLES (cont)
STATUS DISPLAY TABLES (cont)
*Not supported.
†The forced value will be used.
TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS
GENUNIT Operating Type
Control Type
L-Off-Local Off
(ComfortLink Controls= On/Off Switch=Opened)
L-On-Local On
L-Sched-Local On/Off State based on Time Schedules
CCN-Unit is in CCN Control
Remote-On/Off Based on Remote Contact
(not applied to ComfortLink Display)
Master-Unit Operation in Lead/Lag and it is a Master
Local
CCN
Remote
OPER_TYP
ctr_type
Run Status 0 = Off
1 = Running
2 = Stopping
3 = Delay
4 = Tripout
5 = Ready
6 = Override
7 = Defrost
8 = Run Test
9 = Test
STATUS
CCN Chiller Start/Stop Enable/Disable CHIL_S_S forcible
Chiller Occupied? Yes/No CHIL_OCC forcible
Minutes Left for Start 0-15 min min_left
Heat/Cool Status 0 = Cool
1 = Heat
2 = Stand-by
3 = Both
HEATCOOL
Heat/Cool Select 0 = Cool
1 = Heat
2 = Auto
HC_SEL forcible
Heat Reclaim Select
Free Cooling Selct
Ye s / N o
Ye s / N o
RECL_SEL
FC_DSBLE
forcible*
forcible
Alarm State 0 = Normal
1 = Partial
2 = Shutdown
ALM
Current Alarm 1 nnnnn alarm_1
Current Alarm 2 nnnnn alarm_2
Current Alarm 3 nnnnn alarm_3
Current Alarm 4 nnnnn alarm_4
Current Alarm 5 nnnnn alarm_5
Percent Total Capacity nnn % CAP_T
Active Demand Limit Val nnn % DEM_LIM forcible*
Lag Capacity Limit Value nnn % LAG_LIM
Actual Chiller Current nnn amps TOT_CURR forcible†
Chiller Current Limit nnn amps CURR_LIM forcible
Current Setpoint ±nnn.n °F SP
Setpoint Occupied? Yes/No SP_OCC forcible
Setpoint Control Setpt 1
Setpt 2
Ice_sp
4-20mA
Auto
sp_ctrl
Control Point ±nnn.n °F CTRL_PNT forcible*
Controlled Water Temp ±nnn.n °F CTRL_WT
External Temperature ±nnn.n °F OAT
Emergency Stop Enable/Disable EMSTOP forcible
MODES Startup Delay in Effect Yes/No Mode_01
Second Setpoint in Use Yes/No Mode_02
Reset in Effect Yes/No Mode_03
Demand Limit Active Yes/No Mode_04
Ramp Loading Active Yes/No Mode_05
Cooler Heater Active Yes/No Mode_06
Cooler Pumps Rotation Yes/No Mode_07
Pump Periodic Start Yes/No Mode_08
Night Low Noise Active Yes/No Mode_09
System Manager Active Yes/No Mode_10
Master Slave Active Yes/No Mode_11
Auto Changeover Active Yes/No Mode_12
Free Cooling Active Yes/No Mode_13
Reclaim Active Yes/No Mode_14
Electric Heat Active Yes/No Mode_15
Heating Low EWT Lockout Yes/No Mode_16
Condenser Pumps Rotation Yes/No Mode_17
Ice Mode in Effect Yes/No Mode_18
Defrost Active On Cir A Yes/No Mode_19
Defrost Active On Cir B Yes/No Mode_20
Low Suction Circuit A Yes/No Mode_21
Low Suction Circuit B Yes/No Mode_22
Low Suction Circuit C Yes/No Mode_23
High DGT Circuit A Yes/No Mode_24
High DGT Circuit B Yes/No Mode_25
High DGT Circuit C Yes/No Mode_26
High Pres Override Cir A Yes/No Mode_27
High Pres Override Cir B Yes/No Mode_28
High Pres Override Cir C Yes/No Mode_29
Low Superheat Circuit A Yes/No Mode_30
Low Superheat Circuit B Yes/No Mode_31
Low Superheat Circuit C Yes/No Mode_32