Component Test — Complete the following tests to make sure all peripheral components are
operational before the compressors are started.
TOUCH PILOT™ DESCRIPTION NAVIGATOR ITEM NAVIGATOR™
SUBMODE
RANGE CHECK WHEN COMPLETE
Service Test Enable T.REQ Service Test TEST OFF-ON
Compressor A Output CP.A Service Test TEST OFF-ON
Slide Valve Capacity A SLI.A Service Test TEST 0-2
Compressor B Output CP.B Service Test TEST OFF-ON
Slide Valve Capacity B SLI.B Service Test TEST 0-2
Quick Test Enable Q.REQ Service Test QUIC OFF-ON
Circuit A EXV Position EXV.A Service Test QUIC XXX
Circuit B EXV Position EXV.B Service Test QUIC XXX
Cir A Economizer EXV Position ECO.A Service Test QUIC XXX
Cir B Economizer EXV Position ECO.B Service Test QUIC XXX
Circuit A Oil Heater HT.A Service Test QUIC OFF-ON
Circuit A Slide Valve 1 SL1.A Service Test QUIC OFF-ON
Circuit A Slide Valve 2 SL2.A Service Test QUIC OFF-ON
Circuit A Hot Gas Bypass HGP.A Service Test QUIC OFF-ON
Circuit A Oil Solenoid OLS.A Service Test QUIC OFF-ON
Circuit A DGT Cool Solenoid DGT.A Service Test QUIC OFF-ON
Circuit B Oil Heater HT.B Service Test QUIC OFF-ON
Circuit B Slide Valve 1 SL1.B Service Test QUIC OFF-ON
Circuit B Slide Valve 2 SL2.B Service Test QUIC OFF-ON
Circuit B Hot Gas Bypass HGP.B Service Test QUIC OFF-ON
Circuit B Oil Solenoid OLS.B Service Test QUIC OFF-ON
Circuit B DGT Cool Solenoid DGT.B Service Test QUIC OFF-ON
Water Exchanger Pump 1 PMP.1 Service Test QUIC OFF-ON
Water Exchanger Pump 2 PMP.2 Service Test QUIC OFF-ON
Cooler Heater Output CL.HT Service Test QUIC OFF-ON
Cir A Heater Ball Valve BVL.A Service Test QUIC OPEN-CLSE
Cir B Heater Ball Valve BVL.B Service Test QUIC OPEN-CLSE
Chiller Running Output Q.RUN Service Test QUIC OFF-ON
Customer Shutdown Out SHUT Service Test QUIC OFF-ON
Chiller Capacity in 0-10V CATO Service Test QUIC nn.n
Alarm Relay Output ALRM Service Test QUIC OFF-ON
Alert Relay Output ALRT Service Test QUIC OFF-ON