Carrier 30XW150-400 Refrigerator User Manual


 
122
APPENDIX C — CCN TABLES (cont)
STATUS DISPLAY TABLES (cont)
*Not supported.
TABLE DISPLAY NAME RANGE UNITS POINT NAME
FREECOOL* GENERAL PARAMETERS
Free Cooling Disable ? Yes/No FC_DSBLE
LWT – OAT Delta ±nnn.n °F fc_delta
Current Cooling Power nnn °F cool_pwr
Estimated FreeCoo Power nnn °F fc_pwr
Next Session Allowed In nn minutes fc_next
Cooling/FreeCool Timeout nn minutes fc_tmout
Free Cool Conditions OK ? Yes/No fc_ready
Free Cool Request ? Yes/No fc_reqst
Valve Actuators Heaters ? On/Off - FC_HTR
CIRCUIT A
Free Cooling Active Yes/No fc_on_a
Fan Staging Number 1 to 6 FAN_ST_A
3 Way Valve Position nnn % fc_vlv_a
3 Way Valve Status Opening/Closing/... FC_VLV_A
Refrigerant Pump Out On/Off fc_pmp_a
Pump Inlet Pressure ±nnn kPa fc_inp_a
Pump Outlet Pressure ±nnn kPa fc_oup_a
Pump Differential Pressure ±nnn kPa fc_dp_a
EXV Position nnn.n % EXV_A
CIRCUIT B
Free Cooling Active Yes/No fc_on_b
Fan Staging Number 1 to 6 FAN_ST_B
3 Way Valve Position nnn % fc_vlv_b
3 Way Valve Status Opening/Closing/... FC_VLV_B
Refrigerant Pump Out On/Off fc_pmp_b
Pump Inlet Pressure ±nnn kPa fc_inp_b
Pump Outlet Pressure ±nnn kPa fc_oup_b
Pump Differential Pressure ±nnn kPa fc_dp_b
EXV Position nnn.n % EXV_B
CIRCUIT C
Free Cooling Active Yes/No fc_on_c
Fan Staging Number 1 to 6 FAN_ST_C
3 Way Valve Position nnn % fc_vlv_c
3 Way Valve Status Opening/Closing/... FC_VLV_C
Refrigerant Pump Out On/Off fc_pmp_c
Pump Inlet Pressure ±nnn kPa fc_inp_c
Pump Outlet Pressure ±nnn kPa fc_oup_c
Pump Differential Pressure ±nnn kPa fc_dp_c
EXV Position nnn.n % EXV_C