Record Configuration Information
*Not supported.
TOUCH PILOT™
DESCRIPTION
NAVIGATOR
ITEM
NAVIGATOR™
SUBMODE
RANGE DEFAULT ENTRY
Cooler Heater Delta Spt HTR Configuration SERV XX.X 2.0*
Entering Fluid Control EWTO Configuration SERV NO-YES NO
Auto Start When SM Lost AU.SM Configuration SERV NO-YES NO
Brine Freeze Setpoint LOSP Configuration SERV XX.X 34
Brine Flow Switch SP FL.SP Configuration SERV XX.X 1*
Element CCNA Configuration OPTN XXX 1
Bus CCNB Configuration OPTN XXX 0
Baud Rate BAUD Configuration OPTN X 3/9600
Circuit Loading Sequence LOAD Configuration OPTN X EQUAL
Staged Loading Sequence LLCS Configuration OPTN X AUTOMATIC
Ramp Loading Select RL.S Configuration OPTN ENBL-DSBL DSBL
Unit Off to On Delay DELY Configuration OPTN XX 1
Ice Mode Enable ICE.M Configuration OPTN ENBL-DSBL DSBL
Condenser Pumps Sequence HPUM Configuration OPTN X 0/NO PUMP
Cooler Pumps Sequence PUMP Configuration OPTN X 0/NO PUMP
Pump Auto Rotation Delay ROT.P Configuration OPTN XX 48
Pump Sticking Protection PM.PS Configuration OPTN NO-YES NO
Stop Pump During Standby P.SBY Configuration OPTN NO-YES NO
Flow Checked if C Pump On P.LOC Configuration OPTN NO-YES NO
Start Hour (Night Control) LS.ST Configuration OPTN XX.XX 00.00
End Hour (Night Control) LS.ND Configuration OPTN XX.XX 00.00
Capacity Limit (Night Control) LS.LT Configuration OPTN XXX 100
Reverse Alarms Relay RV.AL Configuration OPTN NO-YES NO
Heating OAT Threshold OA.TH Configuration OPTN XX.X 5 F
Current Limit Select CUR.S Configuration OPTN NO-YES NO
Current Limit at 100% CUR.F Configuration OPTN XXXX 2000
Auto Changeover Select AUTO Configuration OPTN NO-YES NO
Cooling Reset Select CRST Configuration RSET X 0
Heating Reset Select HRST Configuration RSET X 0
Demand Limit Type Select DMDC Configuration RSET X 0
mA for 100% Demand Limit DMMX Configuration RSET XX.X 0.0
mA for 0% Demand Limit DMZE Configuration RSET XX.X 0.0
Master/Slave Select MSSL Configuration RSET X 0
Slave Address SLVA Configuration RSET XXX 2
Lead/Lag Select LLBL Configuration RSET X DSBL
Lead/Lag Balance Delta LLBD Configuration RSET XXX 168
Lag Start Timer LLDY Configuration RSET XX 10
Start if Error Higher LL.ER Configuration RSET XX.X 4
Lag Minimum Running Time LAG.M Configuration RSET XXX 0
Lag Unit Pump Control LAGP Configuration RSET X 0
Lead Pulldown Time LPUL Configuration RSET XX 0
Chiller in Series SERI Configuration RSET NO-YES NO