APPENDIX C — CCN TABLES (cont)
MAINTENANCE DISPLAY TABLES (cont)
*Not supported.
TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS
FANCTRL* Cir A SCT Control Point ±nnn.n °F sct_sp_a
Cir A SCT Candidate ±nnn.n °F sct_fu_a
Cir A Fan Cycle Counter ±nnn.n fancyc_a
Cir A Optimal Fan Count ±nnn.n fancop_a
Cir B SCT Control Point ±nnn.n °F sct_sp_b
Cir B SCT Candidate ±nnn.n °F sct_fu_b
Cir B Fan Cycle Counter ±nnn.n fancyc_b
Cir B Optimal Fan Count ±nnn.n fancop_b
Cir C SCT Control Point ±nnn.n °F sct_sp_c
Cir C SCT Candidate ±nnn.n °F sct_fu_c
Cir C Fan Cycle Counter ±nnn.n fancyc_c
Cir C Optimal Fan Count ±nnn.n fancop_c
LAST_POR Power On 1: day-mon-year nnnnnn ddmmyy date_on1
Power On 1: hour-minute nnnn hhmm time_on1
PowerDown 1:day-mon-year nnnnnn ddmmyy date_of1
PowerDown 1:hour-minute nnnn hhmm time_of1
Power On 2: day-mon-year nnnnnn ddmmyy date_on2
Power On 2: hour-minute nnnn hhmm time_on2
PowerDown 2:day-mon-year nnnnnn ddmmyy date_of2
PowerDown 2:hour-minute nnnn hhmm time_of2
Power On 3: day-mon-year nnnnnn ddmmyy date_on3
Power On 3: hour-minute nnnn hhmm time_on3
PowerDown 3:day-mon-year nnnnnn ddmmyy date_of3
PowerDown 3:hour-minute nnnn hhmm time_of3
Power On 4: day-mon-year nnnnnn ddmmyy date_on4
Power On 4: hour-minute nnnn hhmm time_on4
PowerDown 4:day-mon-year nnnnnn ddmmyy date_of4
PowerDown 4:hour-minute nnnn hhmm time_of4
Power On 5: day-mon-year nnnnnn ddmmyy date_on5
Power On 5: hour-minute nnnn hhmm time_on5
PowerDown 5:day-mon-year nnnnnn ddmmyy date_of5
PowerDown 5:hour-minute nnnn hhmm time_of5
LOADFACT CAPACITY CONTROL
Average Ctrl Water Temp ±nnn.n °F ctrl_avg
Differential Water Temp ±nnn.n °F diff_wt
Water Delta T ±nnn.n ^F delta_t
Control Point ±nnn.n °F CTRL_PNT
Reset Amount ±nnn.n ^F reset
Controlled Temp Error ±nnn.n ^F tp_error
Actual Capacity nnn % cap_t
Actual Capacity Limit nnn % cap_lim
Actual Chiller Current nnnn amps TOT_CURR
Chiller Current Limit nnnn amps CURR_LIM
Current At 30% Load A nnnn amps cur_30_a
Current At 30% Load B nnnn amps cur_30_b
Current At 30% Load C nnnn amps cur_30_c
Current At 100% Load A nnnn amps cur100_a
Current At 100% Load B nnnn amps cur100_b
Current At 100% Load C nnnn amps cur100_c
Current Z Multiplier Val ±n.n zm
Load/Unload Factor ±nnn.n 0/0 smz
Active Capacity Override nn over_cap
EHS CAPACITY CONTROL
EHS Ctrl Override nn over_ehs
Requested Electric Stage nn eh_stage
Electrical Pulldown? True/False ehspulld
EXV_CTRL EXV CONTROL
EXV Position Circuit A nnn.n % EXV_A
Discharge Superheat A nnn.n % DSH_A
Suction Superheat A nn.n ^F SH_A
Suction SH Control Pt A nn.n ^F sh_sp_a
Cooler Exchange DT Cir A nn.n ^F pinch_a
Cooler Pinch Ctl Point A nn.n ^F pinch_spa
EXV Override Circuit A nn ov_exv_a
EXV Position Circuit B nnn.n % EXV_B
Discharge Superheat B nnn.n % DSH_B
Suction Superheat B nn.n ^F SH_B
Suction SH Control Pt B nn.n ^F sh_sp_b
Cooler Exchange DT Cir B nn.n ^F pinch_b
Cooler Pinch Ctl Point B nn.n ^F pinch_spb
EXV Override Circuit B nn ov_exv_b
EXV Position Circuit C nnn.n % EXV_C
Discharge Superheat C nnn.n % DSH_C
Suction Superheat C nn.n ^F SH_C
Suction SH Control Pt C nn.n ^F sh_sp_c
Cooler Exchange DT Cir C nn.n ^F pinch_c
Cooler Pinch Ctl Point C nn.n ^F pinch_spc
EXV Override Circuit C nn ov_exv_c
ECONOMIZER CONTROL
Economizer Position A nnn.n % EXV_EC_A
Economizer Superheat A nn.n ^F eco_sha
Economizer SH Setpoint A nn.n ^F ecsh_spa
EXV Override Circuit A nn ov_eco_a
Economizer Position B nnn.n % EXV_EC_B
Economizer Superheat B nn.n ^F eco_shb
Economizer SH Setpoint B nn.n ^F ecsh_spb
EXV Override Circuit B nn ov_eco_b
Economizer Position C nnn.n % EXV_EC_C
Economizer Superheat C nn.n ^F eco_shc
Economizer SH Setpoint C nn.n ^F ecsh_spc
EXV Override Circuit C nn ov_eco_c