Table 12 — Touch Pilot Controller Identification Configuration Table
Table 13 — Touch Pilot™ User Configuration (USERCONF) Table
BACKLIGHT ALWAYS ON? — This configuration is used
to keep the backlight on continuously or to turn it off after 60
seconds with no activity.
Allowable Entries: No/Yes (No=0 or Yes=1)
Default Value: No
FULL ACCESS PASSWORD — This configuration is used
to specify the full access password. Refer to Table 1, Setup
Menu, for additional information on passwords.
Allowable Entries: 0 through 9999
Default Value: 3333
CONTROLLER ID DATA BLOCK NO. VALUE AND RANGE QUALIFIERS
Device Name 1
CHILLDSP
8 character Name field
Default
Optional
Local address 2 115 Default
Bus number 2 0 Default
Device (driver) type 2
0 = Non-bridge
3 = Broadcast Acknowledger
Default
Optional
Primary baud rate 3 38400 Default
Secondary baud rate 3 38400 Fixed
Device description 4
Global Chiller Display
24 character text field
Default
Optional
Device location 4
(Blank)
24 character text field
Default
Optional
Software part number 4 CESR-131363-01 Fixed
Model number 4 (Blank) Fixed
Serial number 4 (Blank) Fixed
Reference number 4 Version 1.0 Fixed
Broadcast address processing list (primary) 5
241-251, 254, 255 enabled
241-255 enabled/disabled
Defaults
Optional
Broadcast address processing list (secondary) 5 none Not applicable
DESCRIPTION LIMITS UNITS NAME DEFAULT
Backlight always on?
No
Ye s
BACKLITE No
Full access password
0
9999
PSWDFULL 3333
Limited access password
0
9999
PSWDLMTD 2222
Active language
0
1
ACTLANG 0
Time format
0
1
TIMEFMT 0
Date format
0
2
DATEFMT 0
Units base
US
Metric
UNITBASE US
Contrast control
Manual
Auto
CONTRAST Auto
Network mode
0
1
NETWORK 0
Network settings
Alarm acknowledger
No
Ye s
ALARMACK No
Broadcast acknowledger
No
Ye s
BROADACK No
Equipment CCN address
Bus number
0
239
EQUIPBUS 0
Element number
1
239
EQUIPELE 1
Control variables
Equipment status (Not Used)
Name
char 8
EQSTATUS NOT USED
Equipment start/stop (Not Used)
Name
char 8
STARSTOP NOT USED
Alarm status (Not Used)
Name
char 8
ALSTATUS NOT USED
Alarm reset (Not Used)
Name
char 8
ALRESET NOT USED