APPENDIX C — CCN TABLES (cont)
STATUS DISPLAY TABLES (cont)
*Not supported.
NOTE: Disable quick test: all the quick test parameters shall be reset to 0.
*Not supported.
NOTE: Disable quick test: all the quick test parameters shall be reset to 0.
*Yes = service test function enable.
†0 = capacity frozen (unchanged).
1 = capacity increase.
2 = capacity decrease.
TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS
QCK_TST1 Quick Test Enable no/Yes Q_TSTRQ forcible
Circuit A EXV Position 0 - 100 % Q_EXVA forcible
Circuit B EXV Position 0 - 100 % Q_EXVB forcible
Circuit C EXV Position 0 - 100 % Q_EXVC forcible
Cir A Economizer EXV Pos 0 - 100 % Q_ECO_A forcible
Cir B Economizer EXV Pos 0 - 100 % Q_ECO_B forcible
Cir C Economizer EXV Pos 0 - 100 % Q_ECO_C forcible
Circuit A Fan Stages 0-10 Q_FAN_A forcible
Circuit B Fan Stages 0-10 Q_FAN_B forcible
Circuit C Fan Stages 0-10 Q_FAN_C forcible
Circuit A Head Press Speed 0 - 100 % Q_VFANA forcible
Circuit B Head Press Speed 0 - 100 % Q_VFANB forcible
Circuit C Head Press Speed 0 - 100 % Q_VFANC forcible
Circuit A Oil Heater Off/On Q_HT_A forcible
Circuit A Oil Solenoid Off/On Q_OILS_A forcible
Circuit A Slide Valve 1 Off/On Q_SLI_1A forcible
Circuit A Slide Valve 2 Off/On Q_SLI_2A forcible
Cir A Heater Ball Valve Off/On Q_BVL_A forcible
Cir A Hot Gas Bypass Off/On Q_HGBP_A forcible
Cir A DGT Cool Solenoid Off/On Q_CDGT_B forcible
Circuit B Oil Heater Off/On Q_HT_B forcible
Circuit B Oil Solenoid Off/On Q_OILS_B forcible
Circuit B Slide Valve 1 Off/On Q_SLI_1B forcible
Circuit B Slide Valve 2 Off/On Q_SLI_2B forcible
Cir A Heater Ball Valve Off/On Q_BVL_B forcible
Cir B Hot Gas Bypass Off/On Q_HGBP_B forcible
Cir B DGT Cool Solenoid Off/On Q_CDGT_B forcible
Circuit C Oil Heater Off/On Q_HT_C forcible
Circuit C Oil Solenoid Off/On Q_OILS_C forcible
Circuit C Slide Valve 1 Off/On Q_SLI_1C forcible
Circuit C Slide Valve 2 Off/On Q_SLI_2C forcible
Cir C Heater Ball Valve Off/On Q_BVL_C forcible
Cir C Hot Gas Bypass Off/On Q_HGBP_C forcible
Cooler Heater Output Off/On Q_CL_HT forcible
Water Exchanger Pump 1 Off/On Q_PMP1 forcible
Water Exchanger Pump 2 Off/On Q_PMP2 forcible
Condenser Pump 1 Off/On Q_HPMP1 forcible
Condenser Pump 2* Off/On Q_HPMP2 forcible
Chiller Ready Output Off/On Q_READY forcible
Chiller Running Output Off/On Q_RUN forcible
Cir A Running Output Off/On Q_RUN_A forcible
Cir B Running Output Off/On Q_RUN_B forcible
Cir C Running Output* Off/On Q_RUN_C forcible
Chiller Capacity in 0-10v 0 – 10.0 volt Q_CATO forcible
Customer Shutdown Out Off/On Q_SHUT forcible
Alarm Relay Output Off/On Q_ALARM forcible
Alert Relay Output Off/On Q_ALERT forcible
TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS
QCK_TST2* Quick Test Enable no/Yes Q_TSTRQ forcible
Air Cond Enter Valve A Off/On Q_HREA_A forcible
Air Cond Leaving Valv A Off/On Q_HRLA_A forcible
Water Cond Enter Valv A Off/On Q_HREW_A forcible
Water Cond Leav Valve A Off/On Q_HRLW_A forcible
Air Cond Enter Valve B Off/On Q_HREA_B forcible
Air Cond Leaving Valv B Off/On Q_HRLA_B forcible
Water Cond Enter Valv B Off/On Q_HREW_B forcible
Water Cond Leav Valve B Off/On Q_HRLW_B forcible
HR Condenser Heater Off/On Q_CD_HT forcible
4 way Valve Circuit A Off/On Q_RV_A forcible
4 way Valve Circuit B Off/On Q_RV_B forcible
Free Cooling Heater On/Off Q_FC_HTR forcible
Free Cool A EXV Position 0 - 100 % Q_FCEXVA forcible
Free Cool B EXV Position 0 - 100 % Q_FCEXVB forcible
Free Cool A Ball Valve Off/On Q_FCBVL_A forcible
Free Cool B Ball Valve Off/On Q_FCBVL_B forcible
TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS
SERV_TST Service Test Enable* no/Yes Q_STREQ forcible
Compressor A Output Off/On Q_CPA forcible
Slide Valve Capacity A 0 - 2† Q_SLIA forcible
Compressor B Output Off/On Q_CPB forcible
Slide Valve Capacity B 0 - 2† Q_SLIB forcible
Compressor C Output Off/On Q_CPC forcible
Slide Valve Capacity C 0 - 2† Q_SLIC forcible