Carrier 30XW150-400 Refrigerator User Manual


 
81
generated if the one of the following configuration errors is
detected by the control. The “nn” refers to the error code listed
in Table 52.
Table 52 — Service Maintenance Alert Codes
Action to be Taken — None.
Reset Method — Manual, after the service has been completed.
Possible Causes — If the Sr-01, 02, or 03 conditions are
encountered, check the following items:
sensor wiring to the Main Base Board
sensor for accuracy
Compressor Motor Temperature Too High
Alarm 132-01 — Circuit A (A1.01)
Alarm 133-01 — Circuit B (B1.01)
Criteria for Trip — The alarm criteria are checked when the
compressor is ON. This alarm will be generated if:
The temperature is greater than 245 F (118 C) and it has
been greater than 212 F (100 C) for 10 consecutive seconds.
The compressor temperature is greater than 232 F (111 C)
for 90 seconds (but less than 250 F [120 C]).
Action to be Taken — The circuit shuts down immediately.
Reset Method — Manual
Possible Causes — If this condition is encountered, check the
following items:
faulty wiring and loose plugs
faulty CPM board
Compressor Motor Temperature Out of Range
Alarm 132-02 — Circuit A (A1.02)
Alarm 133-02 — Circuit B (B1.02)
Criteria for Trip — The alarm criterion is checked when the
compressor is ON. This alarm will be generated if: the temper-
ature is greater than 245 F (118 C) and it has NOT been greater
than 212 F (100 C) for 10 consecutive seconds.
Action to be Taken — The compressor will be stopped.
Reset Method — Manual
Possible Causes — If this condition is encountered, check the
following items:
faulty compressor temperature thermistor
faulty wiring and loose plugs
faulty CPM board
Compressor High Pressure Switch Protection
Alarm 132-03 — Circuit A (A1.03)
Alarm 133-03 — Circuit B (B1.03)
Criteria for Trip — The alarm criterion is checked when the
compressor is ON. This alarm will be generated if the circuit
high-pressure switch (HPS) opens for more than 2 seconds.
The CPM board monitors the HPS switch.
Action to be Taken — The compressor will be stopped.
Reset Method — Manual (reset button on switch)
Possible Causes — If this condition is encountered, check the
following items:
loss of condenser water flow
condenser pump failure
compressor operating beyond the operation envelope
faulty high pressure switch or wiring
faulty CPM board
Compressor Overcurrent
Alarm 132-04 — Circuit A (A1.04)
Alarm 133-04 — Circuit B (B1.04)
Criteria for Trip — The alarm criterion is checked when the
compressor is ON. This alarm will be generated if the CPM
board detects a motor current greater than 93% MTA (must
trip amps) and less than 2 times that for more than 1.7 seconds.
Action to be Taken — The compressor will be stopped.
Reset Method — Manual
Possible Causes — If this condition is encountered, check the
following items:
Compressor operating beyond the operation envelope.
Incorrect MTA setting.
Compressor Locked Rotor
Alarm 132-05 — Circuit A (A1.05)
Alarm 133-05 — Circuit B (B1.05)
Criteria for Trip — The alarm criterion is checked during
start-up when the compressor is ON. This alarm will be gener-
ated if the CPM board detects a high motor current compared
with the MTA (must trip amps) setting for more than 450 ms.
Action to be Taken — The compressor will be stopped.
Reset Method — Manual
Possible Causes — If this condition is encountered, check the
following items:
compressor mechanical failure
unloader slide valve failure
compressor motor failure
Compressor Phase Loss
Alarm 132-06 — Circuit A L1 (A1.06)
Alarm 133-06 — Circuit B L1 (B1.06)
Alarm 132-07 — Circuit A L2 (A1.07)
Alarm 133-07 — Circuit B L2 (B1.07)
Alarm 132-08 — Circuit A L3 (A1.08)
Alarm 133-08 — Circuit B L3 (B1.08)
Criteria for Trip — The alarm criteria are checked during
startup when the compressor is ON. This alarm will be gener-
ated if:
The current unbalance on any of the 3 phases is greater than
48% for more than 1 second continuously during start-up.
The current unbalance on any of the 3 phases is greater than
48% for more than 2 seconds continuously during runtime.
Action to be Taken — The compressor will be stopped.
Reset Method — Manual
Possible Causes — If this condition is encountered, check the
following items:
power failure
blown fuse or tripped circuit breaker
power wiring errors or loose terminals
Compressor Low Current
Alarm 132-09 — Circuit A (A1.09)
Alarm 133-09 — Circuit B (B1.09)
Criteria for Trip — The alarm criteria are checked when the
compressor is ON. This alarm will be generated if:
The current is less than 15% MTA on all three legs for more
than 1 second for Wye-Delta start units.
If the current is less than 15% of MTA on all three legs for
more than 1 second for direct start units.
CODE DESCRIPTION
Sr.01 Circuit A Loss of Refrigerant Charge
Sr.02 Circuit B Loss of Refrigerant Charge
Sr.04 Water Loop Size Warning
Sr.05 Air Exchanger Cleanliness Warning
Sr.06 Cooler Pump 1 Servicing Required
Sr.07 Cooler Pump 2 Servicing Required
Sr.08 Condenser Pump 1 Servicing Required
Sr.09 Condenser Pump 2 Servicing Required
Sr.10 Water Filter Servicing Required
Sr.11 Compressor A Oil Filter Servicing Required
Sr.12 Compressor B Oil Filter Servicing Required