APPENDIX B — NAVIGATOR™ DISPLAY TABLES (cont)
MODE — SET POINTS
ITEM EXPANSION UNITS RANGE COMMENT
WRITE
STATUS
CCN TABLE CCN POINT
PAGE
NO.
COOL COOLING SETPOINTS
CSP.1 Cooling Setpoint 1 XXXX.X
(deg F/deg C)
–20-70 F
(–29-21 C),
Default = 44.0
forcible SETPOINT csp1 25, 41,
55
CSP.2 Cooing Setpoint 2 XXXX.X
(deg F/deg C)
–20-70 F
(–29-21 C),
Default = 44.0
forcible SETPOINT csp2 25, 41,
55
CSP.3 Ice Setpoint XXXX.X
(deg F/deg C)
–20-70 F
(–29-21 C),
Default = 44.0
forcible SETPOINT ice_sp 25, 41,
55
CRV1 Current No Reset Val XX.X (mA) 0-20,
Default = 0
forcible SETPOINT v_cr_no 36
CRV2 Current Full Reset Val XX.X (mA) 0-20,
Default = 0
forcible SETPOINT v_cr_fu 36
CRT1 Delta T No Reset Temp XXX.X (F/C) 0-125 F
(0-69.4 C),
Default = 0
forcible SETPOINT dt_cr_no 35, 36
CRT2 Delta T Full Reset Temp XXX.X (F/C) 0-125 F
(0-69.4 C),
Default = 0
forcible SETPOINT dt_cr_fu 35, 36
CRO1 OAT No Reset Temp XXX.X
(deg F/deg C)
0-125 F
(–18-52 C),
Default = 14.0
forcible SETPOINT oatcr_no
CRO2 OAT Full Reset Temp XXX.X
(deg F/deg C)
0-25 F
(–18-52 C),
Default = 14.0
forcible SETPOINT oatcr_fu
CRS1 Space T No Reset Temp XXX.X
(deg F/deg C)
0-125 F
(–18-52 C),
Default = 14.0
forcible SETPOINT spacr_no 36
CRS2 Space T Full Reset Temp XXX.X
(deg F/deg C)
0-125 F
(–18-52 C),
Default = 14.0
forcible SETPOINT spacr_fu 36
DGRC Degrees Cool Reset XX.X (F/C) –30-30 F
(–16.7-16.7 C),
Default = 0
forcible SETPOINT cr_deg 35, 36
CAUT Cool Changeover Setpt XX.X
(deg F/deg C)
Default = 75.0 Not supported. forcible SETPOINT cauto_sp
CRMP Cool Ramp Loading X.X 0.2-2.0 F
(0.1-1.1 C),
Default = 1.0
forcible SETPOINT cramp_sp 35
HEAT HEATING SETPOINTS
HSP.1 Heating Setpoint 1 XXX.X
(deg F/deg C)
Default = 100 Not supported. forcible SETPOINT HSP.1
HSP.2 Heating Setpoint 2 XXX.X
(deg F/deg C)
Default = 100 Not supported. forcible SETPOINT HSP.2
HRV1 Current to Reset Val XX.X (mA) Default = 0 Not supported. forcible SETPOINT v_hr_no
HRV2 Current Full Reset Val XX.X (mA) Default = 0 Not supported. forcible SETPOINT v_hr_fu
HRT1 Delta T No Reset Temp XXX.X (F/C) Default = 0 Not supported. forcible SETPOINT dt_hr_no
HRT2 Delta T Full Reset Temp XXX.X (F/C) Default = 0 Not supported. forcible SETPOINT dt_hr_fu
HRO1 OAT No Reset Temp XXX.X
(deg F/deg C)
Default = 14.0 Not supported. forcible SETPOINT oathr_no
HRO2 OAT Full Reset Temp XXX.X
(deg F/deg C)
Default = 14.0 Not supported. forcible SETPOINT oathr_fu
DGRH Degrees Heat Reset XX.X (F/C) Default = 0 Not supported. forcible SETPOINT DGRH
HAUT Heat Changeover Setpt XX.X
(deg F/deg C)
Default = 64 Not supported. forcible SETPOINT hauto_sp
HRMP Heat Ramp Loading X.X Default = 1.0 Not supported. forcible SETPOINT hramp_sp
MISC MISC SETPOINTS
DLS1 Switch Limit Setpoint 1 XXX (%) 0-100,
Default = 100
forcible SETPOINT lim_sp1 39, 40
DLS2 Switch Limit Setpoint 2 XXX (%) 0-100,
Default = 100
forcible SETPOINT lim_sp2 39, 40
DLS3 Switch Limit Setpoint 3 XXX (%) 0-100,
Default = 100
forcible SETPOINT lim_sp3
W.SCT Water Val Cond Stp XXX.X
(deg F/deg C)
80-140 F
(26.7-60 C)
Not supported. SETPOINT w_sct_sp 46