Carrier 30XW150-400 Refrigerator User Manual


 
127
APPENDIX C — CCN TABLES (cont)
SETPOINT CONFIGURATION TABLES
*Not supported.
MAINTENANCE DISPLAY TABLES
*Not supported.
NOTES: Tables for display only. Forcing shall not be supported on this maintenance screen.
TABLE DISPLAY NAME RANGE DEFAULT UNITS POINT NAME
SETPOINT COOLING
Cooling Setpoint 1 –20-70 44.0 °F csp1
Cooling Setpoint 2 –20-70 44.0 °F csp2
Cooling Ice Setpoint –20-70 44.0 °F ice_sp
OAT No Reset Value 14-125 14.0 °F oatcr_no
OAT Full Reset Value 14-125 14.0 °F oatcr_fu
Delta T No Reset Value 0-25 0.0 ^F dt_cr_no
Delta T Full Reset Value 0-25 0.0 ^F dt_cr_fu
Current No Reset Value 0-20 0.0 ma v_cr_no
Current Full Reset Value 0-20 0.0 ma v_cr_fu
Space T No Reset Value 14-125 14.0 °F spacr_no
SpaceT Full Reset Value 14-125 14.0 °F spacr_fu
Cooling Reset Deg. Value –30-30 0.0 ^F cr_deg
Cooling Ramp Loading 0.2-2.0 1.0 ^F cramp_sp
HEATING*
Heating Setpoint 1 80-140 100.0 °F hsp1
Heating Setpoint 2 80-140 100.0 °F hsp2
OAT No Reset Value 14-125 14.0 °F oathr_no
OAT Full Reset Value 14-125 14.0 °F oathr_fu
Delta T No Reset Value 0-25 0.0 ^F dt_hr_no
Delta T Full Reset Value 0- 25 0.0 ^F dt_hr_fu
Current No Reset Value 0-20 0.0 ma v_hr_no
Current Full Reset Value 0-20 0.0 ma v_hr_fu
Heating Reset Deg. Value –30-30 0.0 ^F hr_deg
Heating Ramp Loading 0.2-2.0 1.0 ^F hramp_sp
AUTO CHANGEOVER*
Cool Changeover Setpt 39-122 75.0 °F cauto_sp
Heat Changeover Setpt 32-115 64.0 °F hauto_sp
MISCELLANEOUS
Switch Limit Setpoint 1 0-100 100 % lim_sp1
Switch Limit Setpoint 2 0-100 100 % lim_sp2
Switch Limit Setpoint 3 0-100 100 % lim_sp3
Reclaim Setpoint* 95-140 122.0 °F rsp
Reclaim Deadband* 5-27 9.0 °F hr_deadb
Water Val Condensing Stp 80 to 120 86 °F w_sct_sp
TABLE DISPLAY NAME RANGE UNITS POINT NAME WRITE STATUS
BOARD_PN EXV Board Circuit A XXXXXXXX exv_brda
EXV Board Circuit B XXXXXXXX exv_brdb
EXV Board Circuit C XXXXXXXX exv_brdc
AUX Board #1 Part Number XXXXXXXX aux_brd1
AUX Board #2 Part Number XXXXXXXX aux_brd2
AUX Board #3 Part Number XXXXXXXX aux_brd3
AUX Board #4 Part Number XXXXXXXX aux_brd4
AUX Board #5 Part Number XXXXXXXX aux_brd5
EMM NRCP2 Board XXXXXXXX emm_nrcp
Reclaim NRCP2 Board XXXXXXXX rec_nrcp
TCPM Board Comp A XXXXXXXX cpa_vers
Must Trip Amps 0-600 amps cpa_mtam
S1 Config Switch (8 to 1) 00000000 0 cpa_s1_m
TCPM Board Comp B nnnn cpb_vers
Must Trip Amps 0-600 amps cpb_mtam
S1 Config Switch (8 to 1) 00000000 0 cpb_s1_m
TCPM Board Comp C XXXXXXXX cpc_vers
Must Trip Amps 0-600 amps cpc_mtam
S1 Config Switch (8 to 1) 00000000 0 cpc_s1_m
CUR_PHASE Current Phase 1 Comp A 0-600 amps cpa_cur1
Current Phase 2 Comp A 0-600 amps cpa_cur2
Current Phase 3 Comp A 0-600 amps cpa_cur3
Current Phase 1 Comp B 0-600 amps cpb_cur1
Current Phase 2 Comp B 0-600 amps cpb_cur2
Current Phase 3 Comp B 0-600 amps cpb_cur3
Current Phase 1 Comp C 0-600 amps cpc_cur1
Current Phase 2 Comp C 0-600 amps cpc_cur2
Current Phase 3 Comp C 0-600 amps cpc_cur3
DEFROSTM* CIR A DEFROST CONTROL
Exchanger Frost Factor 0-100 % frost_a
Next Sequence Allowed in nnn minutes def_se_a
Defrost Active? True/False mode[19]
Defrost Temperature ±nnn.n °F DEFRT_A
Defrost Duration nnn minutes defr_dua
Fan Sequence Started ? n def_fa_a
Override State nn over_d_a
Mean SST Calculation ±nnn.n °F sst_dm_a
Delta: OAT - Mean SST ±nnn.n ^F delt_a
Reference Delta ±nnn.n ^F delt_r_a
Delta - Reference Delta ±nnn.n °F del_v_a
Frost Integrator Gain n.n fr_int_a
Defrost Fan Start Cal A 0.00 psi def_ca_a
Defrost Fan Offset Cal A 0.00 psi def_of_a
CIR B DEFROST CONTROL
Exchanger Frost Factor 0-100 % frost_b
Next Sequence Allowed in nnn minutes def_se_b
Defrost Active? True/False mode[20]
Defrost Temperature ±nnn.n °F DEFRT_B
Defrost Duration nnn minutes defr_dub
Fan Sequence Started? n def_fa_b
Override State nn over_d_b
Mean SST calculation ±nnn.n °F sst_dm_b
Delta: OAT - Mean SST ±nnn.n ^F delt_b
Reference Delta ±nnn.n ^F delt_r_b
Delta - Reference Delta ±nnn.n ^F del_v_b
Frost Integrator Gain n.n fr_int_b
Defrost Fan Start Cal B 0.00 psi def_ca_b
Defrost Fan Offset Cal B 0.00 psi def_of_b