4 - 25 4 - 25
4.12 Data Check
Whether the monitor screen data created with the GT Designer2 has an error or not is checked.
Open all screens for data check. Unopened screens are not data checked.
Select [Tools] [Data Check] menu.
The data check dialog box is displayed.
Set the check items for data check and click the Check button.
(Setting of GOT-A900 series) (Setting of GOT-F900 series)
Item Description
A F
Check Item Items for data check are checked.
Touch Area
Whether overlap of touch switch functions occurs is checked.
• Touch switches are overlapped.
• Numerical input/ASCII input is overlapped with touch switches.
Key Count Whether the number of touch switch functions exceeds 256 on one screen is checked.
Memory Store
Object
Whether the number of objects (alarm list, trend graph and scatter graph) which set the
memory storage is 17 or more for each object is checked.
Window Screen
Data
Whether the data list or the alarm history is set on the window screen is checked. (The
data list and the alarm history cannot be displayed on the window screen.)
Scroll Object
Whether multiple objects with scroll display (data list, alarm history and alarm list) are set
on one screen is checked.
Report Data
When the report screen is created, whether the numerical print or the comment print is set
on the header is checked.
Number of
object entries
Whether the number of objects that can be registered on one screen exceeds the limit is
checked.
Nest level of set
overlay screens
Whether the nest level of set overlay screens is within 5 that can be set on one screen is
checked.
Key window
screen data
Whether there is any object that cannot be set on the window screen is checked.
Data Area Whether any object is set outside the screen range is checked.
Carry out Checking during
save or transfer
Data check is automatically performed when a project is saved or a monitor screen data is
transferred to the GOT.