PLC User's Manual - Positioning Control Edition
Built-in Positioning Functions
9 One-speed Interrupt constant quantity feed -DVIT Instruction
9.3 Function and Operation
B - 129
A
Common Items
B
Built-in
Positioning
Functions
Apx.
Example
Connection
*1. A device can only be specified if an FX3U/FX3UC PLC Ver.2.20 or later is used.
When using an FX
3UC PLC below Ver.2.20, if "8" is set and then the specified Interrupt Positioning (DVIT)
instruction turns ON, an operation error (error code: K6763) will occur, and the instruction will not cause any
operation.
*2. Y003 can be specified as the pulse output destination only if two FX
3U-2HSY-ADP adapters are connected to
the FX
3U PLC.
*3. After setting a number in the range of 9 to E for the interrupt input signal, if the corresponding Interrupt
Positioning (DVIT) instruction turns ON, an operation error (error code: K6763) will occur, and the instruction
will not cause any operation.
8
*1
Specifies a user
interrupt input command
*1
for the interrupt input
signal.
9 ~ E
*3
Do not specify these values.
F
Set "F" for a pulse output destination device if the device is not used for the Interrupt
Positioning (DVIT) instruction.
Setting value Description of setting
Pulse output destination device User interrupt input command
Y000 M8460
Y001 M8461
Y002 M8462
Y003
*2
M8463