Cautions when connecting special adapters
To use high-speed input/output special adapters only (not to use the other special adapters), it is not
necessary to connect the expansion board.
To use the analog and communication special adapters, be sure to connect the expansion board.
To use high-speed input/output special adapters together with the analog and/or communication special
adapters, connect the high-speed output special adapters to the expansion board (already connected to
the FX
3U PLC) first, and then connect the analog special adapters and/or the communication special
adapter(s).
1.2.4 Special Function Unit/Block
Connect a special function unit/block to the FX3U/FX3UC PLC to control positioning operations. Note that a
special function unit can individually control positioning operations.
1. System configuration for FX3U PLC
Up to 8 special function units/blocks can be connected to the FX3U PLC.
For details on system configuration, refer to the FX
3U Hardware Edition.
2. System configuration for FX3UC PLC
Up to 8
*1
special function units/blocks can be connected to the FX3UC PLC.
FX
2NC-CNV-IF or FX3UC-1PS-5V is needed to connect special function units/blocks.
*1. Up to 7 special function units/blocks can be connected to the FX
3UC-32MT-LT(-2) PLC.
*2. The unit/block number begins with "No. 1" when special function unit/blocks are connected to the
FX
3UC-32MT-LT(-2) PLC.
For details on system configuration, refer to the FX
3UC Hardware Edition.
RD
RDA
RDB
SDA
SDB
SG
SD
FX
3U
PLCExpansion board
High-speed output
special adapter
Analog special adapter
Communication special adapter
Special function block
Special function unit
No.0 No.7
to
Up to 8 units
FX
3U
PLC
POWE
R
ERRO
R
F
P
PG
O
R
P
f
B
f
A
STAR
T
CL
R
DO
G
X
1
X
0
FX
2N
-10PG
Servo motor
(Servo amplifier)
FX
3UC
PLC
FX
3UC
-1PS-5V
or
FX
2NC
-CNV-IF
Special function block
Special function unit
No.0 No.7
to
Up to 8 units
POWER
ERROR
FP
PGO
RP
f
B
f
A
START
CLR
DOG
X1
X0
FX
2N
-10PG
Servo motor
(Servo amplifier)
*2