PLC User's Manual - Positioning Control Edition
Built-in Positioning Functions
12 Examples of Programs
12.4 Positioning Using Batch Setting Method
B - 163
A
Common Items
B
Built-in
Positioning
Functions
Apx.
Example
Connection
12.4 Positioning Using Batch Setting Method
Positioning operation will be performed using the absolute positioning method as shown in the following chart:
For details on input/output assignment, refer to Section 12.1
12.4.1 Setting Using GX Developer
This section describes how to set the positioning parameters using GX Developer Ver.8.23Z.
1 On the project tree displayed on the left side of the screen, double-click on
"Parameter" and then "PLC parameter".
If the project tree is not displayed on the screen, click on "View" in the menu bar, and then click on "Project Data
List".
2 Click on "Memory Capacity", and then enter a check in the "Positioning
Instruction settings" check box.
*1. 9,000 steps are needed to set the positioning data. If there is not enough capacity for programming,
set the "memory capacity" to 16,000 steps.
100
Origin
Output pulse frequency:
100,000 Hz
Acceleration/deceleration time:
100 ms
500,000
Enter a check.
*1