FX
3G
/FX
3U
/FX
3UC
PLC User's Manual - Positioning Control Edition
Built-in Positioning Functions
2 Specifications
2.4 Input Specifications
B - 20
2.4.2 FX3UC Series main unit (24V DC Input)
This section describes the input specifications of the FX3UC Series main unit. Note that the simultaneous
turning-on rate is restricted for the input extension units and the main unit. For details on this restriction, refer
to the following manual:
→ Refer to the FX
3UC Hardware Edition.
*1. If inputs X000 to X007 are assigned to the zero-phase signal of the DSZR instruction or the interrupt
input of the DVIT instruction, the input response time will be as shown in the following table.
*2. PNP open collector transistors are supported only by the FX
3UC-MT/DSS.
*3. The FX
3UC-32MT-LT(-2) uses the display module for monitoring.
1. Internal input circuit
Item 24V DC input specifications
Input signal voltage All inputs 24V DC +20%, -15% / Ripple(p-p): 5 % or less
Input impedance
X000 to X005 3.9kΩ
X006,X007 3.3kΩ
X010 to X017 4.3kΩ
Input signal current
X000 to X005 6mA/24V DC
X006,X007 7mA/24V DC
X010 to X017 5mA/24V DC
Input sensitivity
current
Input ON
current
X000 to X005 3.5 mA or more
X006,X007 4.5mA or more
X010 to X017 3.5mA or more
Input OFF
current
All inputs 1.5mA or less
Input response time All inputs
Approx. 10 ms
*1
Input signal type All inputs
No-voltage contact input
NPN open collector transistor
PNP open collector transistor
*2
Circuit insulation All inputs Photocoupler insulation
Indication of input motion -
Turning on the input will light the LED indicator lamp
*3
Input Input response time
X000 to X005 5µs
X006, X007 50µs
X0
Main unit
X1
Fuse
Class-D grounding
Input impedance
24V DC
COM
·
Sink input type(FX3UC- MT/D, FX3UC-32MT-LT(-2))