Mitsubishi Electronics FX3U Coffeemaker User Manual


 
FX
3G
/FX
3U
/FX
3UC
PLC User's Manual - Positioning Control Edition
Example Connection
Appendix 4. MELSERVO-C Series
Appendix 4-2 High-Speed Output Special Adapter
Apx. - 21
A
Common Items
B
Built-in
Positioning
Functions
Apx.
Example
Connection
*4. To ensure safety, use the forward rotation limit switch and the reverse rotation limit switch on both sides: the PLC side and
the servo amplifier side. Note that the limit switches on the PLC side should be activated slightly earlier than the limit
switches on the servo amplifier side.
*5. Set the pulse output method using the pulse output method setting switch.
Pulse output method setting switch Pulse output method
FP
RP side Forward/reverse pulse train
PLS
DIR side Pulse train + direction
Reverse rotation limit 2
(Servo amplifier side)
Reverse rotation limit 1
(Programmable
controller side)
LSR
Forward rotation limit 2
(Servo amplifier side)
Forward rotation limit 1
(Programmable
controller side)
LSF
Reverse rotation Forward rotation
Servo motor