4.3.2 Immediate Stop of Pulse Output (Pulse Output Stop Command Relay)
During the execution of a positioning instruction, if the pulse output stop command relay is turned on, the
pulses being output will immediately stop.
To output pulses again, turn off the pulse output stop command relay, deactivate (turn off) the positioning
instruction, and then activate the instruction again (turn it on again).
The following table shows the pulse output stop command relay of each pulse output destination device.
*1. Y002 (pulse output destination) cannot be specified when the 14-point or 24-point type FX
3G PLC is
connected.
*2. Devices related to Y003 (pulse output destination) are only valid if two FX
3U-2HSY-ADP adapters are
connected to the FX
3U PLC.
Note:
Use these relays only if immediate stop is absolutely needed to avoid dangers. Since the motor is
immediately stopped, use of these relays may damage the system. For normal STOP operation (decelerate
to stop), use the "instruction OFF" function or "forward/reverse limit relay."
However, note that if the PLSV instruction is used together with the "instruction OFF" function or the "forward/
reverse limit relay" in the M8338 = OFF mode (operation without acceleration/deceleration), operation will
immediately stop.
4.3.3 Designation of Zero Return Direction (DSZR/ZRN Instruction)
Use the DSZR instruction (zero return instruction with DOG search function) or ZRN instruction (zero return
instruction) to specify the zero return direction
*1
. The zero return direction depends on the instruction.
→ For operation of DSZR instruction, refer to Section 6.2.
→ For operation of ZRN instruction, refer to Section 6.3.
*1. If the DSZR instruction (zero return instruction with DOG search function) is used, zero return will be
performed in the direction of the first operation.
1. Zero return instruction with DOG search function (DSZR instruction)
Turn on or off the zero return direction specification relay shown in the following table to specify the zero
return direction.
*1. Y002 (pulse output destination) cannot be specified when the 14-point or 24-point type FX
3G PLC is
connected.
*2. Devices related to Y003 (pulse output destination) are only valid if two FX
3U-2HSY-ADP adapters are
connected to the FX
3U PLC.
Pulse output destination
device
Pulse output stop
command relay
Operation
Y000 M8349
During pulse outputting operation, if the pulse output stop
command relay of the corresponding pulse output
destination device is turned on, the pulse outputting
operation will immediately stop.
Y001 M8359
Y002
*1
M8369
Y003
*2
M8379
Pulse output
destination device
Zero return direction
specification relay
Description of setting
Y000 M8342
To perform zero return in the forward
rotation direction:Turn on the relay.
To perform zero return in the reverse
rotation direction:Turn off the relay.
Y001 M8352
Y002
*1
M8362
Y003
*2
M8372
Reverse rotation limit 2
(Servo amplifier side)
Reverse rotation limit 1
(Programmable
controller side)
LSR
Forward rotation limit 2
(Servo amplifier side)
Forward rotation limit 1
(Programmable
controller side)
LSF
Reverse rotation Forward rotation
Servo motor