5-75
Rosemount Raptor
Section 5. Installing a Raptor Level Gauging System
3. In the Source Device Type/ID/No column, choose a measurement device
such as a pressure transmitter or any other type of instrument.
The default setting lists only the devices mapped to the current tank
position in the 2410 tank database. By using this option you will avoid
mapping to a device on the wrong tank by mistake.
You can choose to show all available devices, or only the devices
mapped to the current tank in the 2410 tank database by selecting the
appropriate radio button.
4. In the Source Parameter column, select the transmitter variable to be
mapped to the tank measurement variable in the first column.
In case User Defined is selected, you may type a description in the
Description of User Def parameter box.
5. When using a Rosemount 2240S Multi-input Temperature Transmitter,
the Raptor system automatically handles mapping of source parameters
to provide correct input for calculation of tank measurement variables
such as Vapor Temperature and Average Temperature.
For Rosemount 644 Temperature Transmitters, tank variables have to be
mapped manually to the appropriate 644 source devices. The output
from each 644 transmitter on the tank is mapped to a temperature tank
variable as shown in the following example with three 644 transmitters
on the tank:
a. Choose Temperature 1 in the Parameter Mapping list for the first
644 Temperature Transmitter.
For the second and third 644 transmitters, choose Temperature 2
and Temperature 3 in the Parameter Mapping list.
b. In the Source Device Type field, for each temperature parameter
(Temperature 1, 2, 3) choose the actual 644 transmitter to be used
as source device.
c. In the Source Parameter list, choose Temperature 1. This is the
source parameter designation of the temperature output from a
Rosemount 644 Temperature Transmitter.
Note that the actual Vapor Temperature and Average Temperature
variables are not mapped to the source devices.
6. Click the Apply button to store the configuration, or click the OK button
to store the configuration and close the window.
Configuration of 644
Temperature Transmitters