5-43
Rosemount Raptor
Section 5. Installing a Raptor Level Gauging System
14. For each tank, specify a Modbus address in the Level Modbus Address
column to be associated with the level gauge. This must be the same
Modbus address as configured in the 2160 FCU Slave Database.
The Level Modbus address is used to identify level gauges when
distributing requests for measurement data from the 2160 Field
Communication Unit.
15. The various non-level devices on a tank are represented by a single ATD
device in the Raptor system.
In tank position 1, the Rosemount Raptor system uses the Modbus
address of the 2410 Tank Hub itself as the ATD Modbus address. In the
example above, the 2410 Tank Hub has Modbus address 101. This
address is automatically used as the ATD Modbus address as well.
For tank positions 2 to 10 you have to specify Modbus addresses in the
ATD Modbus Address column to be associated with the different ATD
devices. The ATD Modbus addresses must be the same as configured in
the 2160 FCU Slave Database.
An empty ATD Modbus address field indicates that no ATD device is
mapped to that particular tank position.
See “Installing a Rosemount 2160 FCU” on page 5-25 and “Examples of
2160 FCU Slave Database Configuration” on page 5-32 for further
information on how the the 2160 slave database is related to the 2410
tank database.
16. Click the Next button to continue the installation procedure.