5-19
Rosemount Raptor
Section 5. Installing a Raptor Level Gauging System
5.3.4 Miscellaneous To change parameters such as type of Tank Capacity Table, or Reference
Temperature, do the following:
1. Select the desired server (e.g. “This Workstation”) in the WinSetup
workspace.
2. Click the right mouse button and choose Setup, or from the Service
menu choose Servers>Setup.
3. In the Server Preferences window select the Miscellaneous tab.
4. Choose a type of Tank Capacity Table (TCT) to be used as default
setting when installing new tanks. The default TCT type will automatically
be chosen when strapping tables are created for new tanks. However,
the TCT type can be changed when the strapping table is specified in the
Tank Capacity Setup window regardless of the settings in the Server
Preferences window.
You can choose between TCT type Raw, International, and Northern.
See the TankMaster WinOpi Reference Manual (Document no.
303028EN) for further information.
5. Specify the maximum number of Digital Alarms that will be used.
6. Specify the Reference Temperature to be used for inventory calculations.
Normally, the standard value 15 °C is used.
7. Click the OK button to save the current settings and close the window.