Emerson 300510EN Yogurt Maker User Manual


 
System Configuration Manual
300510EN, Rev AA
December 2010
Rosemount Raptor
5-54
Section 5. Installing a Raptor Level Gauging System
a. Enter the Unit ID.
When changing the device address, the Unit Id is used as an unique
identifier of the device. The Unit Id can be found on a label mounted
on the device.
b. Set the desired address in the Set Modbus Address input field.
c. Click the OK button to confirm the settings and to close the Change
Address window.
6. In the 5900S RLG Properties/Communication window click the Apply
button to store the Modbus address in the 5900S holding register.
7. In the 5900S RLG Properties window select the Antenna tab:
8. Choose one of the predefined Antenna Types to match the antenna
attached to the 5900S Radar Level Gauge. For predefined antennas, a
number of transmitter parameters such as TCL and Hold Off Distance
are configured automatically in order to optimize measurement
performance.
For non-standard antennas you may choose one of the User Defined
antennas. However, it is recommended that you contact Emerson
Process Management/Rosemount Tank Gauging for advice before using
this advanced option.